Specifications
Features
• 4 image storage
• Camera supervision
• Compatible control panel: PC5015 v2.2 with PC5108L Interface
Module
Power
• 10.5 - 16.0V
DC
• 180mA @ 12V
DC
Video
• Output of 5108L
• Transmits one frame in approximately 10 to 12 seconds
Mounting the Panel
This system should be installed and serviced by qualified security
professionals.
If the DLM-4L is to be used with a security system, install and test the
security system according to the manufacturer’s instructions. For
convenience, install the DLM-4L module close to the security system's
control panel.
1. Remove the printed circuit board and mounting hardware from the
cardboard packaging. It is recommended that the DLM-4L be
mounted in its own cabinet with the 5108L.
2. Before attaching the cabinet to the wall, press the four nylon
mounting studs into the raised mounting holes from the back of
the cabinet.
3. Mount the cabinet securely to the wall. Use appropriate wall
anchors when securing the panel to drywall, plaster, concrete,
brick or other similar surfaces.
4. Press the DLM-4L onto the four mounting studs.
Power Requirements
The DLM-4L v1.0L is used with the PC5108L Video Switcher/Zone
Expansion Interface Module. Refer to the hook-up diagram below
for power connections.
Terminal Connections
Refer to the hook-up diagram below for terminal connections.
Video Connection
The video source for the DLM-4L is provided by the output of the
5108L. If another device such as a VCR or monitor is connected to
the output of the 5108L, then take the output of the device or T-tap
the video connection to provide the necessary video connection to
the DLM-4L.
All cameras should be installed prior to connection of the DLM-4L
and PC5108L. Correct installation, alignment and lens will provide
for maximum results on the Downlook system.
For more information regarding Downlook operation, programming
and testing, see the PC5108L Installation Manual.
Dip Switch Settings
There are 8 dip switches that must be set in the OFF position.
DLM-4L Downlook Still-Frame Video
Transmission Module
Software Version 1.0L I N S T A L L A T I O N I N S T R U C T I O N S
DLM-4L with PC5108L Hook-up Diagram
firealarmresources.com