Supreme Heating Aqua-Gen 3BR Installation Instructions Manual Download Page 1

 

Aqua-Gen 3BR INSTRUCTIONS 

 
 

INSTALLATION INSTRUCTIONS 

 
 
CONTROLLER: 

Find a suitable location to mount the control box*

radio note

. The controller must be installed out of direct 

weather  and  no  closer  than  3m  from  the  waters  edge.  Lift  up  the  two  mounting  tabs  and  use  two 
appropriate screws to mount the control box to the wall, keeping in mind that the power cable is 1.8m 
long and should be plugged directly into a general power outlet, not into an extension lead. Do not drill 
through the box. 
 
 

SOLAR PUMP: 

The solar pump plugs into the left side 240Vac socket marked as PUMP. 
 
 

TEMPERATURE SENSOR: 

The pool temperature sensor must be fitted into the suction line of the solar pump, as close to the pool 
as practical, preferably in a position out of direct sunlight. It is recommended that a 14.5mm hole be 
drilled in the PVC pipe, this can be carried out using a Dontek PD01 grinding drill or a small pilot hole 
can  be  drilled  and  a  14.0mm  drill-bit  used  spinning  in  a  counter  clockwise  direction  to  minimise  the 
chance of shattering pipe. Insert the grommet into the pipe and gently push in the black sensor barb. 
The green sensor plug is to be fitted to the plug socket marked POOL, in some cases there is some 
benefit to cable tie 30cm of wire from the pool temperature sensor to the pipe and insulate this section 
(some ambient differences can travel up the tinned copper wire and affect the sensor reading). 

 
All temperature sensor cables must NOT be run parallel to power cables and should never be 
cable  tied  to  power  cables. 

All  cable  run  lengths  should  be  less  than  50m  if  possible.  Cable  ties 

should be used to fasten the sensor cable to the cold water inlet pipe making sure that the ties are 
approximately 10mm from PVC fittings. Cable ties should be tightened only firm, over tightening can 
cause breaks in the outer PVC if not careful. If the cable is to be run under ground a conduit must be 
used  to  protect  the  wire  and  there  is  to  be  no  cable  joins  within,  conduit  ends 

must

  be  sealed  to 

prevent water ingress. 

Any excess cable should be removed and re-fitted ensuring that the wire 

ends are tinned with solder.

 

 
 
REMOTE TEMPERATURE ROOF SENSOR: 

The

 

roof  temperature  sensor  must  be  fitted  into  a  small  piece  of  solar  collector  or  equivalent  and 

attached  to  the  roof.  The  best  location  is  within  an  arms  length  of  the  gutters  edge  of  the  house  or 
shed as long as the sensor end is not shaded and is on a roof of similar aspect of the main collector. It 

must not

 be fitted on top of the solar collector or fitted to high points on the roof like Ridge Capping as 

false readings will be detected. 
 
This unit has been designed to eliminate the need to run a temperature sensor cable from the solar 
controller  to  the  roof;  this  is  replaced  by  a  battery  powered  transmitter  that  transmits  the  roof 
temperature. The roof sensor plugs into the radio remote temperature transmitter socket at the bottom 
of the unit (run the cable behind the box). 

Summary of Contents for Aqua-Gen 3BR

Page 1: ...wire and affect the sensor reading All temperature sensor cables must NOT be run parallel to power cables and should never be cable tied to power cables All cable run lengths should be less than 50m i...

Page 2: ...l plug from the RUN position from the 3 pin header and placing it onto TEST The Aqua Gen 3 BR will enter into a RX TEST mode Verify that every 8 9 seconds the LCD displays the temperature e g TEST 32...

Page 3: ...dio transmitter batteries have expired this will prevent the controller from operating Replace batteries and re select any operating mode to clear the battery low message Note Batteries may begin to l...

Page 4: ...ce manual mode is selected the pump will start if it has been off or stop if it has been on running After 30 minutes manual mode will time out and return to Summer Mode with a default temperature limi...

Page 5: ...ure is less than the pipe temperature plus this value adjust with the UP DOWN button press SELECT to accept Default values are 8 for RUN and 4 for END these are the optimal values for maximum efficien...

Page 6: ...5 C no calibration is required 4 The sensor cable with the thin trace is the positive and is fitted to the right hand side of the green plug when looking at the plug screws incorrect polarity will be...

Page 7: ...struction may void the warranty Warranty does not cover travel costs to or from installation site Return to supplier for repair Customer Record to be retained by the customer Dealer Installer Name ___...

Reviews: