Installation
900077-00, 01/2018
Innovative Hearth Products
DRL6500 Linear Direct-Vent Gas Fireplaces
25
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Clearance to combustibles
Maintain the minimum clearance to combustibles (e.g., framing, attic, ceiling insulation, etc.).
For all vertical runs:
• 1” (26 mm) from all sides
NOTE:
Attic insulation shield (H3908) must be installed when blown or loose-fill insulation is used, and is recommended
for all attic installations.
For all horizontal/inclined runs:
• 3” (77 mm) from the top
• 1” (26 mm) from the sides
• 1” (26 mm) from the bottom
8.
Install the Vent System
Install the Vertical Termination Vent System
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according
to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards
of CAN/CGA-B149.1 in Canada.
Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier.
Dégagement conforme aux codes d’installa tion locaux et aux exigences du foumisseunde gaz.
Vertical vent systems terminate through the roof. The minimum vent height above the roof and/or adjacent walls is
specified in ANSI Z223.1 (In Canada, the current CAN/CGA-B149.1 installation code) by major building codes. Always
consult your local codes for specific requirements. A general guide to follow is the gas vent rule
(
Table 6
)
.
The following figures and their associated vertical vent tables illustrate the various configurations that are possible for
use with these fireplaces. Secure Vent
®
pipe is shown in these figures; Secure Flex
®
pipe may also be used. A table
summarizes each configuration’s minimum and maximum vertical and horizontal length parameters for a variety of
applications.
1.
Refer to
Figure 23
,
Table 19
, and
Table 20
on
Pages 28-29
to select the type of vertical installation desired. Elbows
are available in 90° and 45° configurations. Refer to
Figure 20
on
Page 23
for the SV4.5E45 and SV4.5E90 elbow
dimensional specifications.
Vertical (Straight) Installation
1. Determine the number of straight vent sections required
—See
Effective Vent Length on
Page 22
for more
information. Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists.
Figure 18 - Vertical (Straight) Installation
Vertical
firestop/spacer
See
Table 8
SecureVent
®
vent sections
Max. 60 ft
(18 m)
Min. 6 ft
(1.8 m)
Vertical termination
Flashing and
storm collar