state. When WUW priority mode is on the main the letter B is show in the lower right 
corner of the display. 
 

 

ATTENTION:  The  boiler  should  have  non-return  valves  mounted  on  the 
central heating pump circuit and the hot consumption water pump circuit. 
A valve mounted on the WUW pump will prevent domestic hot  water from 
being drawn from the water heater.

 

 
10.9.3. Parallel pumps 
In this mode, both pumps are running simultaneously given that the pump activation 
temperature  is  reached  (set  by  default  to  35°C).  The  central  heating  pump  runs  all 
the  time,  while  the  domestic  hot  water  WUW  pump  stops  after  the  set  point 
temperature is  reached.  The  pump  is  then  reactivated once  when  the  temperature 
drops  by  2°C.  Changing  the  desired  DHW  temperature  can  be  done  by  pressing 
button  EXIT  (holding  down  for  a  few  seconds).  The  display  will  show  the  WUW 
temperatures  screen.  Set  temperature  can  be  changed  with  the  buttons  UP  and 
DOWN. After few seconds the display will return to its previous state. 

 

 

ATTENTION:  In  this  mode,  a  non-return  valve  should  be  fitted  to  maintain 
different temperatures in the water heater and in the house.

 

 

After  activation  of  the  parallel  pumps  function,  three  items  appear  on  the  display. 
Starting from the left, these are:  
Boiler  Temperature  (CH);  Domestic  Hot  Water  Temperature  (WUW)  and  SET  point 
Temperature (SET). When parallel pumps mode is activated the letter R is shown in 
the lower right corner of the display. 

 

10.9.4.  Summer mode

 

When  the  function is enabled,  only  the  WUW  pump  is  running  in  order  to  heat  the 
water  for  domestic  use.  The  pump  is  switched  on  upon  reaching  a  predefined 
activation  threshold  (see  the  pump  activation  temperature  function)  and  will  run 
until  the  set  point  temperature  has  been  reached.  The  pump  will  start  again  when 
the  temperature  drops  below  the  set  hysteresis.  While  in  the  Summer  Mode,  the 
letter L is displayed in the bottom right corner of the main screen.  

Summary of Contents for BURNiT Magna WBS-A 450

Page 1: ...TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL EN Model serial Version i0 1 1 Solid fuel boiler WBS A 450 Magna...

Page 2: ......

Page 3: ...0 6 INSTALLATION OF THE HEATING BOILER 10 6 1 Requirements 10 6 2 Assembly disassembly of the boiler housing 11 6 3 Check door tightness 12 7 SETUP OF THE HEATING BOILER 13 7 1 Connecting the boiler t...

Page 4: ...nd correct installation start up and trouble free operation and maintenance of the heating boiler The heating boiler can be used for heating rooms only in the manner described in this manual Take note...

Page 5: ...structions Customer must undergo boiler operation maintenance training by authorized installer service shop 1 2 2 Instructions to installation user DANGER of intoxication or explosion Toxic gases may...

Page 6: ...inimum clearances in your country may differ from the ones specified bellow Please consult with your installer The minimum distance from the heating boiler or exhaust gas pipe to objects or walls must...

Page 7: ...c hot water DHW circuits upon constant temperature indication signals The power of the intake fans can be regulated in a broad range depending on the used type and condition of the fuel and also the c...

Page 8: ...agram 2 Relation between wood heating value and water content Table 2 Heating value of the most common wood species 4 TRANSPORTATION OF THE BOILER We recommend to transport the heating boiler to the i...

Page 9: ...the lower part of the boiler are provided transportation openings Important When installing the boiler the wooden pallet onto which the boiler is placed must be removed by unscrewing the bolted conne...

Page 10: ...ecessary to maintain combustion Boilers must not be placed in inhabitable rooms All boiler rooms must have correctly calculated vent depending on the boiler output The vent must be protected by means...

Page 11: ...Rightside upper front panel 1 6 Leftside upper front panel 1 7 Rightside upper back panel 1 8 Leftside upper back panel 1 9 Frontside upper left panel 1 10 Frontside upper right panel 1 11 Frontside c...

Page 12: ...boiler s air distribution body and fixing it to panels 4 and 13 using 5 25mm screws 8 pcs Step 13 Fix the main switchboard 14 to panel 5 using 5 12mm screws 2 pcs Step 14 Fix the blower fans 16 onto t...

Page 13: ...outlet must be sturdy and properly sealed to avoid gas leak and allow for easy access for cleaning on the inside The inner section of the flue outlet must not be greater than the effective section of...

Page 14: ...ssel No shut off fittings may be installed between the relief valve expansion vessel and boiler It is mandatory to install a three way valve Laddomat or similar or a four way mixing valve which to ens...

Page 15: ...sure you are using dry fuel When using fuels with high percent humidity it is possible that the boiler works for a certain period after refilling with reduced power capacity while the fuel dries enou...

Page 16: ...lectrical mains which complies with the local regulations Warning Be careful when connecting the circulation water pumps the controller is only capable of sending signals voltage for controlling the p...

Page 17: ...TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL 17 EN Diagram 6...

Page 18: ...in a closed system Such connections must be performed by a technician service shop authorized for such operations Diagram 7 1 Thermostat 6 Hot water collector 2 Expansion vessel 7 Heating circuit 2 p...

Page 19: ...LATION and OPERATION MANUAL 19 EN 7 4 2 Connection of BURNiT WBS A Magna boiler in an open system Diagram 8 1 Cold water inlet 5 Return valve 2 Drainage 6 Insulation 3 Air vent line 7 Hot water outlet...

Page 20: ...the summer 9 BOILER OPERATION 9 1 Loading and ignition the boiler When igniting the boiler for the first time a condensate is formed which is later drained this is not a fault in the boiler The fuel...

Page 21: ...ts as they obstruct normal heat transfer 2 Dismount the internal protective grates that lay onto the heat exchanging pipes in the combustion chamber of the boiler Clean thoroughly the heat exchanging...

Page 22: ...period of time at an output lower than 50 When using a circulation pump closed system it is necessary to put a three way thermostatic valve which provides the optimal temperature of the return water T...

Page 23: ...lue Explanation of buttons Navigation arrow UP PLUS Navigation arrow DOWN MINUS MENU button Enter menu approve settings EXIT button canceling settings Power switch ON OFF Fans CH PUMP Central heating...

Page 24: ...damping time the controller will switch to the damping mode While in this mode the fan is deactivated and the display shows Damping 10 2 Main page During normal operation in only CH mode the LCD displ...

Page 25: ...executive element can be switched off and on independently from all the other elements Pressing down MENU starts the fan which remains turned on until the next pressing of the MENU button Pressing do...

Page 26: ...re It is the difference between the set temperature that is the boiler required temperature and the actual boiler temperature e g if the set temperature has the value of 55 C and the hysteresis is 5 C...

Page 27: ...m right corner of the main screen 10 9 2 DHW priority WUW Priority Activating the DHW priority will cause the regulator to switch into the DHW priority mode In this mode the WUW pump is activated unti...

Page 28: ...will show the WUW temperatures screen Set temperature can be changed with the buttons UP and DOWN After few seconds the display will return to its previous state ATTENTION In this mode a non return va...

Page 29: ...ATTENTION Do not connect the room regulator to external electricity source 10 11 Suspension operation This option allows the user to set the working time of the fans in suspension mode above the set t...

Page 30: ...s damaged or overheated the fan is disabled Automatic sensor check In case when the CH temperature sensor is missing or damaged an alarm is activated which additional reports the fault on the display...

Page 31: ...at 63 C and it will remain in the duty mode maintaining the priority temperature of 65 C Fuse The controller has a network protection WT 3 15 A tube fuse ATTENTION Higher current ratings may cause da...

Page 32: ...nd low chamber resistance Combustion chamber with three way passage of the exhaust gases through the smoke pipes protected by a water mantle Easy cleaning of the fume exhaust tubes thanks to the inspe...

Page 33: ...igh temperature insulation of mineral wool 4 Fume exhaust tube 5 Water mantle 6 Three pass flue gas flow 7 Combustion chamber 8 Blower fans 9 Metal grate 10 Transportation openings 11 Ash removal door...

Page 34: ...TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL 34 EN 12 2 Technical parameters...

Page 35: ...ll load h 5 5 3 5 Operating temperature range Max temperature C 65 85 95 Exhaust gas temperature operation mode C 150 180 Power consumption W 760 Power supply V Hz 230 50 Operating pressure Bar 4 Weig...

Page 36: ...r recyclable waste containing materials with adverse effect on health and environment According to Directive 2002 96 EC regarding electrical and electronic equipment waste disposal thereof is required...

Page 37: ...2 TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL...

Page 38: ...TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL...

Page 39: ......

Page 40: ...aria t 359 54 874 555 f 359 54 874 556 e mail ftrade sunsystem bg 13 Chelopeshko Shose Str 1839 Sofia Bulgaria t 359 2 903 97 80 f 359 54 874 556 e mail sales sunsystem bg www sunsystem bg ISO 9001 20...

Reviews: