Draught depends on the diameter,
height, uneven sections along the
chimney surface and differences
in temperature of combustion
products and outside air. We
recommend that you use chimney
fitted with flue terminal. Heating
specialist must calculate the
precise sizing of the chimney.
We recommend that the stove be installed
as close as possible to the system’s
exhaust gas extraction system (the flue).
The maximum permitted length of duct
pipe between the stove and the flue is 3
m, whereas no horizontal section longer
than 0.5 m is allowed.
7.2. Type of tubes for exhaust gas system
(chimney)
The tubes must be solid, smooth inside,
mad of steel and must be accompanied by
silicone gaskets.
The diameter of tubes long up to 3 m.
must be 80 mm. The diameter of tubes
long more than 3 m. must be minimum
100 mm. as it is necessary to obtain the
required draught of the chimney.
Do not connect the exhaust gas
system to a chimney in which
already is connected another
stove, boiler or ventilation
system!
7.3. Connecting of outer tube for fresh
air flow
For proper functioning and distribution
of the temperature the pellet stove must
receive enough fresh air flow and to be
well positioned (a special opening for
fresh air could be done for example).
The flue opening area should be at
least 100 cm2. If the premises has an
air outflow/suction system installed, a
relevant fresh air inflow must be provided
for.
This may be carried out through providing
continuous ventilation from another
premises with no fireplace or other air-
intaking system in operation.
Such premises exclude bedrooms,
bathrooms, or premises with increased
fire hazard, such as garages, basements,
or flammable material storage rooms.
If such room has already another heating
appliance installed (e.g. a fireplace,
a heater etc.) or another source of
hazardous gases, then the new stove must
be provided with an additional source of
fresh air from outdoors.
The same provision goes for any
subsequently added heating devices.
Example: Connection of tube for fresh air
flow directly from the outside
For proper functioning of the pellet stove
it is recommended to make a direct
connection from outside the room with
steel pipe 80 мм. with silicon gasket. The
part of the tube that goes outside the
room must be situated downwards 90° - in
this way a protection against wind, water,
etc. is achieved.
Upon such direct connection the following
distances should be observed:
- 1.5 m from the floor
- 1.5 m from horizontal ducting section
- 0.3 m from doors and windows, whereas
pipes must run above them
- 2.0 m from the exhaust gas system.
Summary of Contents for BURNIT AMBIENT V2 4G 10 Plus
Page 18: ...18 TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL...
Page 20: ...20 TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL 9 2 Controller Menus...
Page 22: ...22 TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL...
Page 32: ...ISO 9001 2008 BUREAU VERITAS Certification tel 359 700 17 343 www burnit bg...