71
figure 7-16
NS Protection(Passive Valid)
7.8.3 Power Regulation Parameters
Active Power Regulation
Tap
Settings→Power Regulation Parameters→Active Power Regulation
to enter the
screen, as shown in the following figure.
figure 7-17
Active Power Regulation
table 7-8 Active Power Regulation
Parameter
Definition/Setting
Description
Range
Active power soft start
after fault
The switch for enabling/dis-
abling the soft start function
after a fault occurs.
Enable/Disable
Active power soft start
time after fault
Time that the soft start takes to
raise the power from 0 to
100% rated power.
1s~1200s
Active power gradient
control
Switch for enabling/disabling
the active power rate settable
function.
Enable/Disable
Active power decline
gradient
The decline rate of inverter ac-
tive power per minute.
1%/min~6000%/min