Please ensure that the inverter is equipped with DC PID before setting PID parame-
ters. If it is equipped with AC PID, please refer to the EMU200A user manual for PID
parameter settings. The PID type of the inverter is subject to the actually received
inverter.
7.8.3 Power Regulation Parameters
Active Power Regulation
Tap
Settings→Power Regulation Parameters→Active Power Regulation
to enter the
screen, as shown in the following figure.
figure 7-14
Active Power Regulation
table 7-7 Active Power Regulation
Parameter
Definition/Setting
Description
Range
Active power soft start
after fault
The switch for enabling/dis-
abling the soft start function
after a fault occurs.
Enable/Disable
Active power soft start
time after fault
Time that the soft start takes to
raise the power from 0 to
100% rated power.
1s~1200s
Active power gradient
control
Switch for enabling/disabling
the active power rate settable
function.
Enable/Disable
Active power decline
gradient
The decline rate of inverter ac-
tive power per minute.
1%/min~6000%/min