14
4.2.
Modes Transition
When energized, the SG250K3 switches among different modes as pictured
below.
Start-up
Run
Commissionling
Stand-by
Fault
Fault occurs
1.Fault resolved for 5 minutes
2.Vpv>450V for 1 minutes
Key-stop
Emer-stop
1.
Turn the start/stop switch to start position
2.
Release the emergency stop button
3.
Stop the inverter through touch screen menu
to clear the
“
Emer-stop
”
state
4.
Start the inverter through touch screen menu
Vpv>450
V for 1 m
inutes
Normal Operation
Vpv>450V for 1 minutes
Ipv
≈
0A for 3 minutes
Press ES button
(OR)Turn the start/stop switch to stop position
Stop the inverter through touch screen menu
1.
Turn the start/stop switch to start position
2.
Release the emergency stop button
3.
Start the inverter through touch screen menu
Figure 4-1 Transition of operation states
The states displayed in the touch screen menu are explained in Table 4-1.
Table 4-1 State explanations of SG250K3
State
Simple Explanation
Key-stop
The inverter is stopped by touch screen stop command
Emer-stop
1.
The inverter is stopped by pressing down the
emergency button
2.
The inverter is stopped by turning the start/stop
switch to the “stop” position
Stand-by
The inverter is ready to switch to Run mode
Start-up
The inverter is ready to switch to Run mode(only
appear once during commissioning )
Run
The inverter is performing correct PV generation
operation
Fault
A fault is happened*
1,2
*1.the fault type will be displayed like “Vdc-high”or “Vac-low” etc.
* 2.The “Com-flt” will also be displayed in the state position in the touch screen,
but in fact it is not a state, it means there is a fault between touch screen and DSP,
which also means that users can not check or set parameters through touch screen
control menu during this fault. But this fault will not stop the inverter, which is
different from Fault condition.
Summary of Contents for SG250K3
Page 1: ...SG250K3 Grid Connected Inverter Operation Manual SG250K3 3A E Ver21 200903 Version 2 1...
Page 2: ...Release History Version Release Date 2 1 Mar 2009 Author Approved By Chen Wei Zhao Wei...
Page 9: ...Safety Instructions Chapter 1 provides some important safety instructions about SG250K3...
Page 13: ...4 Introduction Chapter 2 provides basic information about SG250K3...
Page 18: ...9 Commissioning Chapter 3 describes the verification and commissioning of SG250K3...
Page 21: ...12 Operation Chapter 4 provides instructions about how to operate the SG250K3...
Page 38: ...29 5 History Events 6 History faults 7 History data...
Page 51: ...42 5 Input the limit data for the running parameter at the Set value column...
Page 53: ...44 5 Input the limit data for the protection parameter at the Set value column...
Page 62: ...53 Appendix...