50
F
Fiig
gu
urre
e 5
5--5
5 Configuration of dip switch (N≥15)
The length of the RS485 cable should be no longer than 1,200m.
If multiple inverters are connected to the data collectorLogger3000, the
number of permissible daisy chains and the number of devices allowed to be
connected should meet the requirements (refer to the user manual for the
Logger3000).
5.9.3 Connection Procedure(Terminal Block)
RS485 communication cables should be shielded twisted pair cables or
shielded twisted pair Ethernet cables.
There are four RS485 communication terminals COM1, COM2, COM3and
COM4 on the bottom of the inverter. Please choose according to the actual
situation.
Step 1
Strip the protection layer and insulation layer by appropriate length.
Step 2
Loosen the swivel nut of the communication terminal and select an appropriate seal
according to cable outer diameter. Lead the cable through the swivel nut and seal
successively.
User Manual