35
In Australia, a RCD is not required according to the local standard AS3000-2018 when either
of the following installation methods is adopted if the PV array capacitance to ground is large
(such as a tin roof):
•
Use heavy duty conduits (such as metal bushing) when run PV and AC cables through
Cavity walls.
•
Route the PV and AC cables through pipes (PVC or metal tubing), lay the cables and in-
stall them.
5.5.2 Assembling the AC Connector
step 1 Unscrew the swivel nut of the AC connector.
step 2 Thread the AC cable of appropriate length through the swivel nut, the sealing ring and the
housing.
step 3 Remove the cable jacket by less than 45 mm, and strip the wire insulation by 12 mm–16 mm.
User Manual