30
The grounding screws have been anchored to the side of the inverter before
delivery, and do not need to be prepared.
There are two grounding terminals. Use at least one of them to ground the
inverter.
-- -- E
En
nd
d
5.6
AC Cable Connection
5.6.1 AC Side Requirements
Connect the inverter to the grid only after getting an approval from the local
electric power company.
Before connecting the inverter to the grid, ensure the grid voltage and frequency
comply with requirements, for which, refer to ""T
Te
ec
ch
hn
niic
ca
all D
Da
atte
e"". Otherwise, contact the
electric power company for help.
A
AC
C C
Ciirrc
cu
uiitt B
Brre
ea
akke
err
An independent three-pole or four-pole circuit breaker is installed on the output side of
the inverter to ensure safe disconnection from the grid.
IIn
nvve
errtte
err M
Mo
od
de
ell
R
Re
ec
co
om
mm
me
en
nd
de
ed
d rra
atte
ed
d
vvo
olltta
ag
ge
e
R
Re
ec
co
om
mm
me
en
nd
de
ed
d rra
atte
ed
d
c
cu
urrrre
en
ntt
SG125HX
800V
125A
Never connect a load between the inverter and the circuit breaker.
Multiple inverters cannot share one circuit breaker.
M
Mu
ullttiip
plle
e IIn
nvve
errtte
errss iin
n P
Pa
arra
alllle
ell C
Co
on
nn
ne
ec
cttiio
on
n
If multiple inverters are connected in parallel to the grid, ensure that the total number of
parallel inverters does not exceed 30. Otherwise, please contact SUNGROW for
technical scheme.
M
MV
V T
Trra
an
nssffo
orrm
me
err
The MV transformer used together with the inverter should meet the following
requirements:
•
The transformer may be a distribution transformer, and it must be designed for the
typical cyclical loads of a PV system (load in the day and no load at night).
•
The transformer may be of the liquid-immersed type or dry type, and shield winding
is not necessary.