QP_EnableMode
Unconditional activation/
deactivation of Q(P) function
Yes/No
Q(U)Curve
Select the corresponding
curve according to local
regulations
Curve A/Curve B/Curve C*
QU_V1
Pre-set grid voltage U1 that
is reactive according to the
grid voltage
80.0%~100.0%
QU_Q1
Pre-set proportion of reactive
power according to the grid
voltage U1
[-60.0%~0]* Overload
Rate/1000
QU_V2
Pre-set grid voltage U2 that
is reactive according to the
grid voltage.
80.0%~100.0%
QU_Q2
Pre-set proportion of reactive
power according to the grid
voltage U2.
[-60.0%~60.0%]* Overload
Rate/1000
QU_V3
Pre-set grid voltage U3 that
is reactive according to the
grid voltage.
100.0%~120.0%
QU_Q3
Pre-set proportion of reactive
power according to the grid
voltage U3.
[-60.0%~60.0%]* Overload
Rate/1000
QU_V4
Pre-set grid voltage U4 that
is reactive according to the
grid voltage.
100.0%~120.0%
QU_Q4
Pre-set proportion of reactive
power according to the grid
voltage U4.
[0~60.0%]* Overload Rate/
1000
QU_EnterPower
Active power for Q(U)
function activation
20.0%~100.0%
QU_EXitPower
Active power for Q(U)
function deactivation
1.0%~20.0%