43
The RS485-1 crimp and the RJ45 interface can be applied to applications where
multiple inverters communicate in a daisy-chain form.
A 120Ω resistor can be connected in parallel between RS485-1 A/B pins by configuring
the dip switch.
RS485-1 crimp interface and RJ45 interface serve as the same function with
different wiring manner.
5.10.2 RS485 Communication System
SG Modbus can be adopted.
S
Siin
ng
glle
e--iin
nvve
errtte
err C
Co
om
mm
mu
un
niic
ca
attiio
on
n S
Syysstte
em
m
In case of a single inverter, communication cable connection requires only one RS485
cable.
ffiig
gu
urre
e 5
5--5
5 Single-inverter Connection
M
Mu
ullttii--iin
nvve
errtte
err C
Co
om
mm
mu
un
niic
ca
attiio
on
n S
Syysstte
em
m
In case of multiple inverters, all the inverters can be connected via RS485 cables in the
daisy chain manner.
User Manual
Summary of Contents for SG125HX
Page 1: ...User Manual PV Grid Connected Inverter SG125HX SG125HX UEN Ver14 202105 WWW SUNGROWPOWER COM...
Page 2: ......
Page 6: ......
Page 10: ......
Page 32: ...22 E En nd d 4 Mechanical Mounting User Manual...