User Manual
43
5.3.1 PV Input Configuration
The following requirements must be adhered to. Failure to do so may
void any or all warranty rights.
Make sure the voltage of each PV array is less than 1500V at all times.
Permanent damage may occur otherwise.
Make sure the max. short-circuit current of the DC side is within the
permissible range. Permanent damage may occur otherwise.
● ● ●
● ● ●
●
●
●
●
●
●
PV Arrays
DC Combiner box
SG125HV
String #1
String #N
The SG125HV-30 is a single stage inverter with only one MPPT. To make
full use of the DC input power and reduce the power loss caused by
mismatch, the type and rating of the PV modules connected to one
inverter should be the same, including:
the same PV module model;
the same number of PV modules;
the same angle of tilt of the PV modules;
5.3.2 Requirements for OT/DT Terminal (DC)
OT/DT terminals (not included in the delivery scope) are required for fixing AC
cables to the terminal block. Purchase the OT/DT terminals according to the
following requirements.
Specification: M10;
(Single-hole terminal) Dimensions: a
≤
43mm / 10.5mm
≤
b
≤
12.5mm / c
≤
13mm