47
9 Appendix
9.1
Technical Parameters
9.1.1
Electrical Parameters
Input parameters (DC side)
Parameter
SG1250UD
SG1500UD
Max. DC voltage
1,100Vdc
1,100Vdc
Start-up voltage
540V
600V
MPP voltage range
520V
~
1000V
580V
~
1000V
Min. operating voltage
520V
580V
Max. input current
2,712A
2,896A
Output parameters (AC side)
Parameter
SG1250UD
SG1500UD
Nominal output power
1,250kW
1,500kW
Max. output power
1,375kW
1,650kW
Max. output AC
2,222A
2,381A
Nominal grid voltage
360Vac
400Vac
Gird
voltage
range
(three-phase)
288Vac ~414Vac(settable)
320Vac~460Vac(settable)
Nominal grid frequency
50Hz/60Hz
Grid frequency range
45~55Hz/55~65Hz(settable)
THD
<3% (at nominal power)
DC current injection
<0.5% (nominal output current)
Adjustable power factor
0.8 (leading)~0.8 (lagging)
9.1.2
Mechanical Parameters
Parameter
SG1250UD
SG1500UD
Dimensions (W×H×D)
2,150mmx2,120mmx850mm
Weight
1,900kg
9.1.3
System Parameters
Parameter
SG1250UD
SG1500UD
Max. efficiency
99%
Euro efficiency
98.7%
Ingress of protection
IP65
Night power consumption
<40W
Auxiliary power supply
2kW / 220V
Operating temperature
-35
℃
~
+
60
℃
(
>
50
℃
derating)
Cooling method
Forced air cooling
Operating humidity
0
~
95% (Non-condensing)
Max. operating altitude
4,500m (
>
3,000m derating)