114
table 10-1 Correspondence between number of inverters and maximum wiring distance
Number of
inverter
Maximum wiring distance(unit:m)
16AWG / 1.31mm
2
17AWG / 1.026mm
2
1
13030
10552
2
6515
5276
3
4343
3517
4
3258
2638
5
2606
2110
6
2172
1759
7
1861
1507
8
1629
1319
9
1448
1172
10
1303
1055
11
1185
959
12
1086
879
13
1002
812
14
931
754
15
869
703
16
814
660
17
766
621
18
724
586
19
686
555
20
652
528
21
620
502
22
592
480
23
567
459
24
543
440
25
521
422
In case the specification of the cable used is not included in the Table above, when
there is only one inverter, ensure that the line impedance of the input node is less
than 300Ω; and when there are multiple inverters connected in the daisy chain, en-
sure that the impedance is less than 300Ω/number of inverter.