27
•
Determine whether an AC circuit breaker with greater overcurrent capacity is re-
quired based on actual conditions.
•
Multiple inverters cannot share one circuit breaker.
•
Never connect a load between the inverter and the circuit breaker.
Residual Current Monitoring Device
With an integrated universal current-sensitive residual current monitoring unit included, the
inverter will disconnect immediately from the mains power once a fault current with a value
exceeding the limit is detected.
However if an external residual current device (RCD) (type A is recommended) is mandatory,
the switch must be triggered at a residual current of 300 mA (recommended). RCD of other
specifications can also be used according to local standard.
In Australia, a RCD is not required according to the local standard AS3000-2018 when either
of the following installation methods is adopted if the PV array capacitance to ground is large
(such as a tin roof):
•
Use heavy duty conduits
(
such as metal bushing
)
when run PV and AC cables through
Cavity walls.
•
Route the PV and AC cables through pipes (PVC or metal tubing), lay the cables and in-
stall them.
Multiple Inverters in parallel Connection
If multiple inverters are connected in parallel to the grid, ensure that the total number of par-
allel inverters does not exceed 5. Otherwise, please contact SUNGROW for technical
scheme.
5.5.2 Assembling the AC Connector (< 15 kW)
The AC terminal block is on the bottom side of the inverter. AC connection is the three-
phase-four-wire grid + PE connection (L1, L2, L3, N, and PE).
step 1 Unscrew the swivel nut of the AC connector.
step 2 Take out the spring-loaded terminal from the housing.