22
Step 3
Connect the stripped cable to the RS485 ports of the Logger1000, as shown in the
figure below.
RS485A is connected to port A while RS485B is connected to port B.
The RS485 communication cable must be the shielded twisted pair with the
shielding layer single-point grounded.
When a multi-core multi-strand copper wire cable is used, crimp an
appropriate euro style terminal at the communication cable head and then
connect it to the RS485 port of the Logger1000.
Step 4
Connect the Logger1000 to the inverter.