Sun Gold Power Co.,Ltd
www.
sungoldpower.com
25
4.6 Battery type parameters
For
Lead-acid
Battery
:
Battery type
Parameters
Sealed lead
acid battery
(SLD)
Colloidal lead
acid battery
(GEL)
Vented lead
acid battery
(FLD)
User-defined
(USE)
Overvoltage disconnection
voltage
60V
60V
60V
60V
Equalizing charge voltage
58.4V
56.8V
59.2V
40
~
60V
(
Adjustable
)
Boost charge voltage
57.6V
56.8V
58.4V
40
~
60V
(
Adjustable
)
Floating charge voltage
55.2V
55.2V
55.2V
40
~
60V
(
Adjustable
)
Undervoltage alarm voltage
44V
44V
44V
40
~
60V
(
Adjustable
)
Low voltage disconnection
voltage
42V
42V
42V
40
~
60V
(
Adjustable
)
Discharge limit voltage
40V
40V
40V
40
~
60V
(Adjustable)
Over-discharge delay time
5s
5s
5s
1
~
30s
(Adjustable)
Equalizing charge duration
120 minutes
-
120 minutes
0
~
600
minutes
(Adjustable)
Equalizing charge interval
30 days
-
30 days
0
~
250
days
(Adjustable)
Boost charge duration
120 minutes
120 minutes
120 minutes
10
~
600
minutes
(Adjustable)