Lifting Station Type ABS Sanimax

1051-00

15970278EN (08/2019)

en

Installation and Operating Instructions

Summary of Contents for ABS MF 154

Page 1: ...www sulzer com Lifting Station Type ABS Sanimax 1051 00 15970278EN 08 2019 en Installation and Operating Instructions ...

Page 2: ...ting unit 7 5 Installation 8 5 1 Cable inlet 8 5 2 Discharge Line 8 5 2 1 Installation example Sanimax R202 and R202 C 9 5 3 Electrical connection 9 5 4 Washing machine connection 10 5 5 Hand wash basin connection 10 5 6 Shower connection only used with Sanimax R202 R202 C 10 6 Maintenance 11 6 1 General maintenance hints 11 6 2 Cleaning the lifting unit 11 Lifting Station Type ABS Sanimax R 202 M...

Page 3: ...result in medium or water escaping If damage may occur due to the specific usage measures are required to avoid such damage arising In this respect taking account of the conditions in question particularly use of an off grid alarm system use of an emergency generator and provision of an additional and appropriately connected second unit are to be considered Sanimax R 202 R 202C Sanimax MF 154 324 ...

Page 4: ...er backwash level is the maximum possible water level in the public sewer network Information on this can be obtained from your Local Authority If the backwash level has not been fixed by the Local Authority then the surface level of the roadway at the connection point is taken to be the level If the effluent does not give rise to foul odours then a water tight connection tank fitted with a lid is...

Page 5: ...head MF 154HW 3 m 4 1 Design of the lifting unit 1 2 3 4 5 6 7 1053 01 1 2 3 4 5 6 7 1054 01 Figure 2 Sanimax R202 R202 C Figure 3 Sanimax MF 1 Discharge line 5 Vertical inflow in tank cover 2 Non return valve 6 Tank venting with integral odour filter and overflow protection 3 Synthetic tank triangular shape 7 Sealed cable entry 4 Wastewater pump with level control Supplied as standard Sanimax R20...

Page 6: ... brought above the backwash loop 180 bend and then allowed to flow by gravity into the collection sewer or channel regulations EN 12056 and DIN 1986 100 The discharge line should be laid so that it is not affected by frost The discharge line should not be connected to a downpipe No other discharge lines or inflows should be connected to the discharge line Select a suitable tank port for the discha...

Page 7: ... Electrical connection Before operating have a qualified person check that all required electrical protective measures are present Earthing neutral line earth leakage circuit breakers etc must correspond to the regulations of your local Electricity Supply Provider and must function perfectly ATTENTION Cross section and voltage drop of the power line must correspond with the local Electricity Suppl...

Page 8: ...nnecting a shower one of the lower tank ports should be used The height difference between the floor of the shower and the floor of the tank of the lifting unit should be to EN DIN in accordance with the illustration In the case of a greater distance between the Sanimax R202 R202 C and the shower basin it is necessary to make an addition to allow for the recommended fall for gravity flow The showe...

Page 9: ...ll bearings together with monitoring devices ensure optimum reliability of the pump provided that installation and usage is in accordance with our operating instructions Should a problem arise do not improvise but ask your Sulzer Service Centre for assistance In order to ensure a long running life regular checks and care are recommended The Sulzer Service Organisation will be glad to advise you on...

Page 10: ...10 ...

Page 11: ...11 ...

Page 12: ...Sulzer Pump Solutions Ireland Ltd Clonard Road Wexford Ireland Tel 353 53 91 63 200 Fax 353 53 91 42335 www sulzer com ...