ECO ARC 600
3-3
Revision 1/10/08
3.2
Energy supply
Caution!
Work on electrical systems and equipment should only be performed
by a qualified electrician.
3.2.1 Electrical supply
Note
•
Making currents from major loads and other mains fluctuations
interrupt spraying.
•
400 V mains voltage should only be under-/ overshot by a maxi-
mum of 5%.
4 - wire mains connection
3 Phases
1 Earth
black, brown, grey
yellow-green
Mains voltage
400 V, 50 - 60 Hz
Nominal current
< 38 A
Fuse
50 A
Cable extension
Dimensions (for Cu)
(No. of leads x lead-profile in mm²)
up to 20 m
5 x 6
up to 50 m
5 x 10
up to 100 m
5 x 16