Suburban SA25N Owner'S Operation And Installation Manual Download Page 4

7

Figure 9 - Locations of Screws in Back
of Furnace Cabinet (25,000 BTU/Hr
Model)

Figure 10 - Locations of Screws in
Back of Furnace Cabinet (40,000
BTU/Hr Model)

Figure 11 - Removing Screws on Lower
Flange (40,000 BTU/Hr Model Shown)

Figure 13 - Location of Knockout Plug

Figure 14 - Inserting Pipe through
Knockout Hole

Figure 12 - Disconnecting Gas Inlet Pipe
(40,000 BTU/Hr Model Shown)

Figure 8 - Connecting Gas from Inside of
Room

INSTALLATION

(Continued)

Connecting Furnace to Gas
Supply at Front of Furnace

1. Locate gas inlet pipe on lower, right

front of furnace (see Figure 8).

2. Connect 3/8" NPT pipe or nipple to

gas inlet pipe (see Figure 8). See

Providing Gas Piping to Furnace 

for

correct gas pipe installation.

Connecting Furnace to Gas 
Supply at Rear of Furnace

1. Remove the two screws in back of fur-

nace cabinet located by the exhaust
vent(s) (see Figures 9 and 10).

2. Remove two screws on front lower

flange that attach furnace flange to
furnace cabinet flange (see Figure
11). 

Note:

 40,000 BTU/Hr model has

a bottom shield (see parts list, page
19, for location). Removing two
screws will detach bottom shield.

3. Slide furnace out of furnace cabinet.

4. Locate gas inlet pipe on lower, right

front of furnace.

5.

40,000 BTU/Hr Model Only: 

Remove

screw holding gas inlet pipe clamp to
furnace. (See Figure 12).

6. Disconnect gas inlet pipe from 3/8"

manifold elbow. Turn gas inlet pipe
counterclockwise to disconnect (see
Figure 12).

7. Rotate the 3/8" manifold elbow 90

/

 so

the opening is pointing downward
(see Figure 12).

8. Locate knockout plug in furnace cabi-

net. Knockout plug is in lower left rear
of furnace cabinet (as viewed from
rear, see Figure 13). Remove
knockout plug.

9. Slide furnace back into furnace cabi-

net. Make sure exhaust tube gaskets
are in place. Make sure exhaust and
intake vent tubes extend into vent
caps on back of cabinet. Replace two
screws by exhaust vent(s) removed in
step 1.

10.

25,000 BTU/Hr Model: 

Replace two

screws removed in step 2. Attach fur-
nace flange and furnace cabinet
lower flange together.

40,000 BTU/Hr Model: 

Place bottom

shield back in place. Replace two
screws removed in step 2. Attach bot-
tom shield, furnace flange, and
furnace cabinet lower flange together.

11. Run 3/8" pipe or nipple through

knockout hole. Connect 3/8" pipe or
nipple to manifold elbow (see Figure
14). See 

Providing Gas Piping to

Furnace 

for correct gas pipe instal-

lation.

 

CAUTION: Lightly apply pipe  joint

sealant to male threads before
connecting. Use pipe joint sealant
that is resistant to liquid petroleum
(LP) gas.

12. Check connections for gas leak.

 

WARNING:  Never use an open

flame to check for a leak. Apply a
mixture of liquid soap and water to
all joints. Bubbles forming show a
leak. Correct all leaks at once.

13. Caulk around pipe or nipple. This pre-

vents cold air entering knockout hole.

8

INSTALLATION

(Continued)

Providing Gas Piping to Furnace - Propane (LP) Gas Only
See Next Page for Natural Gas Piping

You must provide gas piping from gas source to furnace. The gas piping must be in a vertical position where it connects to the furnace.
This prevents interference with front cover installation.

Consult your local gas company for proper routing of the gas lines.

Pipe size is determined by the length of pipe from the gas source to the furnace and the total BTU load on the gas source.

Add the total BTUs required for all appliances connected to the gas source including this furnace. Divide this number by 2500. This
will give you the approximate cubic feet per hour needed.

Example:

40,000

BTU/Hr

+ 15,000

BTU/Hr for other gas appliances

55,000

BTU/Hr total

55,000 ÷ 2500 = 22

Locate 22 or higher on chart below.

According to the chart below, you should use 40 feet or less of 3/8" pipe, 125 feet 
or less of 1/2" pipe, etc....

MINIMUM
RON PIPE
      SIZE

LENGTH OF PIPE (FEET)

10

20

30

40

50

60

70

80

90

100

125

150

175

200

3/8"

47

32

26

22

19

18

16

15

14

13

12

11

10

1/2"

87

61

48

42

37

33

30

28

26

25

22

20

18

17

3/4"

184

126

100

86

76

69

63

59

55

52

48

42

39

36

1"

344

232

189

162

142

129

119

112

106

99

86

79

73

66

1¼"

696

484

391

331

291

265

245

232

212

202

182

166

149

139

1½"

1060

729

590

504

444

404

371

351

324

305

272

252

232

212

2"

2022

1392

1094

961

842

762

696

656

616

576

517

470

430

404

2½"

3182

2188

1790

1524

1326

1226

1127

1060

994

928

829

749

969

649

3"

5635

3911

3116

2718

2387

2154

1989

1856

1724

1657

1458

1326

1226

1127

4"

11602

7956

6431

5503

4906

4508

4110

3845

3580

3381

2983

2718

2519

2320

IMPORTANT:

 Check gas line pressure at gas meter before connecting furnace to gas line. Gas line pressure must be no less than

11 inches of water and no greater than 13 inches of water. Gas pressures and input to the burners must not exceed the rated input
and pressure shown on the rating plate. For propane/LP gas, manifold pressure should be 10 inches of water. For elevations above
2000 feet, reduce rating 4% for each 1000 feet above sea level (U.S.A. only).

         CAUTION: Never connect heater directly to the propane/LP supply. This heater requires an external regulator (not
supplied). Install the external regulator between the heater and propane/LP supply.

The installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming
gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, heater regulator damage could
occur. Install external regulator with the vent pointing down. Pointing the vent down protects it from freezing rain or sleet.

Summary of Contents for SA25N

Page 1: ...on or near the appliance Never place any objects on the furnace Surface of furnace becomes very hot when running furnace Keep children and adults away from hot surface to avoid burns or clothing ignit...

Page 2: ...re you have all items below electric drill drill bits Phillips screwdriver hammer pipe wrench stud locator or small finishing nails equipment shutoff valve supplied test gauge connection see Figure 15...

Page 3: ...re no pipes wiring or anything else that wouldinterferewith installing thermostat Do not mount thermostat to stud If there are any obstructions choose a new location 3 Provide two 18 gauge insulated s...

Page 4: ...iquid soap and water to all joints Bubbles forming show a leak Correct all leaks at once 13 Caulk around pipe or nipple This pre vents cold air entering knockout hole 8 INSTALLATION Continued Providin...

Page 5: ...15 Install an equipment shutoff valve in an accessible location The equipment shutoff valve is for turning on or shutting off the gas to the appliance Apply pipe joint sealant lightly to male threads...

Page 6: ...explosion may result causing propertydamage personal injury or loss of life A This appliance does not have a pilot It is equipped with an ignition device which automatically lights the burner Do not...

Page 7: ...a qualified service person Furnace may need more frequent cleaning due to excessive lint from carpeting bedding material pet hair etc CAUTION Labelall wiringprior to disconnection when servicing contr...

Page 8: ...e is established the sensing probe will sense the presenceofburnerflame and open the glo bar circuit The glo bar will then stop glowing It is important to determine the type of problem being experienc...

Page 9: ...ty coverage for parts replaced under warranty PARTS UNDER WARRANTY Contact authorized dealers of this product If they can t supply original replacement part s call Suburban Manufacturing Company Custo...

Page 10: ...MODEL KEY NO PART NUMBER DESCRIPTION QTY KEY NO PART NUMBER DESCRIPTION QTY 1 121357 Screw 6 x 5 8 4 14 021175 Combustion Chamber Radiation 2 232773 Module Board 1 Shield Assembly with Gasket 1 2A 232...

Page 11: ...N QTY 1 350086 Room Air Wheel 1 15 390296BK Combustion Air and Motor 2 121252 Screw 10 x 3 8 5 Cover Assy Housing 1 3 121247 Screw 2 56 x 5 8 2 16 070386 Combustion Air Housing Gasket 1 4 230510 Micro...

Page 12: ...ew 6 x 3 8 2 17 230560 Limit Switch 1 2 231950 Flame Sensing Probe 1 18 062563 Ignition Control Mounting 1 3 063018 Glo Bar Retainer 1 19 232773 Module Board 1 4 120158 Screw 8 x 3 8 6 19A 232774 Wiri...

Page 13: ...10 24 x 1 2 2 2 121252 Screw 10 x 3 8 8 16 070362 Universal Bushing 1 3 350088 Room Air Wheel CW Rotation 1 17 070406 Combustion Air Housing Gasket 1 4 390328BK Room Air Blower Housing 18 120158 Scre...

Page 14: ...XCLUSIVE AND MAY NOT BE ALTERED ENLARGED OR CHANGED BY ANY DISTRIBUTOR DEALER OR OTHER PERSON WHOMSOEVER ALL REPLACEMENT PARTS ASSUME AS THEIR WARRANTY PERIOD ONLY THE REMAINING TIME PERIOD OF THIS WA...

Reviews: