Table 513:
Time synchronization PTP: IEC/IEEE 61850-9-3
Supported types of clock
Boundary Clock (BC), Ordinary Clock (OC),
Transparent Clock (TC)
Accuracy
According to standard IEC/IEEE 61850-9-3
Number of nodes
According to standard IEC/IEEE 61850-9-3
Ports supported
All rear Ethernet ports
16.2
Parameter setting groups
IP1745-1 v1
16.2.1
Functionality
M12006-6 v7
Use the six different groups of settings to optimize the IED operation for different
power system conditions. Creating and switching between fine-tuned setting sets,
either from the local HMI or configurable binary inputs, results in a highly
adaptable IED that can be applied to a variety of power system scenarios.
16.2.2
Function block
IP9661-1 v1
M12010-3 v3
ACTVGRP
ACTGRP1
ACTGRP2
ACTGRP3
ACTGRP4
ACTGRP5
ACTGRP6
GRP1
GRP2
GRP3
GRP4
GRP5
GRP6
SETCHGD
REMSETEN
IEC05000433-3-en.vsd
IEC05000433 V3 EN-US
Figure 295:
ActiveGroup function block
16.2.3
Signals
IP14073-1 v2
PID-6558-INPUTSIGNALS v6
Table 514:
ACTVGRP Input signals
Name
Type
Default
Description
ACTGRP1
BOOLEAN
0
Selects setting group 1 as active
ACTGRP2
BOOLEAN
0
Selects setting group 2 as active
ACTGRP3
BOOLEAN
0
Selects setting group 3 as active
ACTGRP4
BOOLEAN
0
Selects setting group 4 as active
ACTGRP5
BOOLEAN
0
Selects setting group 5 as active
ACTGRP6
BOOLEAN
0
Selects setting group 6 as active
1MRK 505 384-UEN A
Section 16
Basic IED functions
Breaker protection REQ650 2.2 IEC
657
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...