![Subaru impreza 2017 Owner'S Manual Download Page 531](http://html.mh-extra.com/html/subaru/impreza-2017/impreza-2017_owners-manual_1389064531.webp)
The front port is only intended for PCM600 communication,
maintenance, training and test purposes due to risk of interference
during normal operation.
14.4.2
Communication interfaces and protocols
GUID-35C845D3-574A-40D1-AEF1-9E0D330E31DE v7
Table 395:
Supported station communication interfaces and protocols
Protocol
Ethernet
Serial
100BASE-FX (ST
connector)
Glass fibre (ST
connector)
EIA-485
IEC 61850–8–1
●
-
-
DNP3
●
●
●
IEC 60870-5-103
-
●
●
● = Supported
14.4.3
Settings
PID-6702-SETTINGS v3
Table 396:
IEC61850-8-1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
GOOSEPortEd1
AP_FRONT
AP_1
AP_2
AP_3
AP_4
AP_5
AP_6
-
-
AP_1
Selection of GOOSE port (only for
IEC61850 Ed1)
ProtocolEdition
Ed 1
Ed 2
-
-
Ed 1
Protocol Edition
RemModControl
Off
Maintenance
All levels
-
-
Off
Remote Mode Control
AllowSimulation
No
Yes
-
-
No
Allow simulated GOOSE values or
simulated sampled measurand values
RemSetControlEd2
Disabled
Enabled
-
-
Disabled
Changing settings over 61850 enabled
(only for IEC61850 Ed2)
ResvTmsEd2
1 - 3600
s
1
60
Reservation time (only for IEC61850
Ed2)
1MRK 505 384-UEN A
Section 14
Station communication
Breaker protection REQ650 2.2 IEC
525
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...