alarm, two time delays
tTempAlarm
or
tTempLockOut
have been included. If the
temperature goes above the settings for more than these time delays, the
corresponding alarm TEMPALM or lockout TEMPLO will be initiated. The
SETTLO binary input is used for setting the temperature lockout TEMPLO. The
TEMPLO output retains the last value until it is reset by using the binary input
RESETLO. The binary input BLKALM can be used for blocking the alarms, and
the BLOCK input can block both alarm and the lockout indications.
The output ALARM goes high if the level alarm condition or the temperature
alarm condition exists in the transformer. The output ALARM can be blocked by
activating BLOCK or BLKALM inputs.
The output LOCKOUT goes high if the pressure lockout condition or the
temperature lockout condition exists in the transformer and it resets by using the
binary input RESETLO. The output LOCKOUT can be blocked by activating
BLOCK input.
11.3.8
Technical data
GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v7
Table 335:
SSIMLTechnical data
Function
Range or value
Accuracy
Oil alarm level
1.00-100.00
±10.0% of set value
Oil lockout level
1.00-100.00
±10.0% of set value
Temperature alarm level
-40.00-200.00
±2.5% of set value
Temperature lockout level
-40.00-200.00
±2.5% of set value
Time delay for oil alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is
greater
Reset time delay for oil alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is
greater
Time delay for oil lockout
(0.000-60.000) s
±0.2% or ±250ms whichever is
greater
Time delay for temperature
alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is
greater
Reset time delay for
temperature alarm
(0.000-60.000) s
±0.2% or ±250ms whichever is
greater
Time delay for temperature
lockout
(0.000-60.000) s
±0.2% or ±250ms whichever is
greater
11.4
Breaker monitoring SSCBR
11.4.1
Identification
GUID-0FC081B2-0BC8-4EB8-9529-B941E51F18EE v7
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Breaker monitoring
SSCBR
-
-
1MRK 505 384-UEN A
Section 11
Monitoring
Breaker protection REQ650 2.2 IEC
433
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...