6.6.3
Function block
M12627-3 v8
LCPTTR
I3P*
BLOCK
BLKTR
ENMULT
AMBTEMP
SENSFLT
RESET
TRIP
START
ALARM
LOCKOUT
IEC13000199-1-en.vsd
IEC13000199 V1 EN-US
LFPTTR
I3P*
BLOCK
BLKTR
ENMULT
AMBTEMP
SENSFLT
RESET
TRIP
START
ALARM
LOCKOUT
IEC13000301-1-en.vsd
IEC13000301 V1 EN-US
Figure 53:
LCPTTR/LFPTTR function bloc
6.6.4
Signals
PID-3908-INPUTSIGNALS v7
Table 67:
LCPTTR Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Group signal for current input
BLOCK
BOOLEAN
0
Block of function
BLKTR
BOOLEAN
0
Block of trip
ENMULT
BOOLEAN
0
Current multiplyer used when THOL is for two or
more lines
AMBTEMP
REAL
0
Ambient temperature from external temperature
sensor
SENSFLT
BOOLEAN
0
Validity status of ambient temperature sensor
RESET
BOOLEAN
0
Reset of internal thermal load counter
PID-3909-INPUTSIGNALS v9
Table 68:
LFPTTR Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Group signal for current input
BLOCK
BOOLEAN
0
Block of function
BLKTR
BOOLEAN
0
Block of trip
ENMULT
BOOLEAN
0
Current multiplyer used when THOL is for two or
more lines
Table continues on next page
1MRK 505 384-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
141
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...