Troubleshooting Guides
Integrated
(700-
3
BASE)
Series
8-4
#3758424 - Revision B - December, 2005
EC
TEST / ACTION
20
21
22
23
24
30
A.
With cold evap. (< 10°F), initiate Manual Defrost, then initiate Diagnostic Mode (press UNIT ON/OFF key every 20
seconds to keep in Diagnostic Mode) and observe evap. temp. If temp. exceeds 45°F and defrost lasts longer then
5 minutes, error code is false. Clear error code. If error code is not false:
1.
Check continuity of Grey/White wire from defrost heater to J2-3 on control board. Reconnect / repair
Grey/White wire.
2.
While in defrost, check for 115V AC at P2 on control board. If no voltage, replace board.
3.
Check continuity of Blue wire from defrost terminator to P2 on control board. Reconnect / repair Blue wire.
4.
Check resistance of defrost heater (see wire diagram for proper resistance). Replace heater if defective.
5.
Check electrical connections and operation of defrost terminator (Cut-in 30°F/Cut-out 70°F). Reconnect /
repair or replace terminator.
6.
Reference wiring diagram to identify components in same White wire circuit as defrost heater. Check all White
wire electrical connections and continuity from defrost heater to P4 on control board.
A.
With cold evap. (< 10°F), initiate Manual Defrost, then initiate Diagnostic Mode (press UNIT ON/OFF key every 20
seconds to keep in Diagnostic Mode) and observe evap. temp. If temp. does not exceed 105°F, error code is false.
Clear error code. If error code is not false:
1.
Check Blue wire connection at control board (P2). If connected to wrong pin, connect correctly.
2.
Check Grey/White wire connection at control board (J2-3). if connected wrong or bad connection, reconnect /
repair.
3.
Check for proper mounting & location of evap. thermistor, defrost heater & terminator. Remount correctly.
4.
Check for electrical short of Blue wire to another circuit. Repair Blue wire &/or electrical connections.
5.
Check operation of defrost terminator (Cut-in 30°F / Cut-out 70°F). Replace if defective.
A.
With cold evap. (< 10°F), initiate Manual Defrost. If compressor starts 5 minutes (10 minutes in 700TF/I-2V) after
defrost is initiated, check Grey/White wire and continuity from defrost heater to J2-3 on control board. Reconnect /
repair Grey/White wire.
A.
With cold evap. (< 10°F), initiate Manual Defrost. If compressor starts 5 minutes (10 minutes in 700TF/I-2V) after
defrost is initiated, check Grey/White wire connections and continuity from defrost heater to J2-3 on control board.
Reconnect / repair Grey/White wire.
B.
Check for proper mounting and location of evap. thermistor, defrost heater & terminator. Remount correctly.
C. Check Blue wire connection at control board (P2). If connected to wrong pin, connect correctly.
D
Check for electrical short of Blue wire to another circuit. Repair Blue wire &/or electrical connections.
A.
With cold evap. (< 10°F), initiate Manual Defrost, then initiate Diagnostic Mode (press UNIT ON/OFF key every 20
seconds to keep in Diagnostic Mode) and observe evap. temp. If temp. exceeds 45°F, error code is false. Clear
error code. If error code is not false:
1.
Check Blue wire connection at control board (P2). If connected to wrong pin, connect correctly.
2.
Verify proper location of Grey/White wire at control board (J2-3). if connected wrong or bad connection, recon-
nect / repair.
3.
Check for proper mounting & location of evap. thermistor, defrost heater & terminator. Remount correctly.
A.
Check for jammed cube in icemaker.
B.
Reference wiring diagram to identify components in same White wire circuit as water valve solenoid. Check all
White wire electrical connections and continuity from water valve solenoid to P4 on control board.
ERROR CODE TROUBLESHOOTING GUIDE
NOTE:
After repairs, always clear Error Codes by pressing Bell ON/OFF key for 15 seconds.
Summary of Contents for 700-3 BASE
Page 2: ......
Page 12: ...Installation Information Integrated 700 3 BASE Series 2 4 3758424 Revision B December 2005 ...
Page 40: ...Electronic Control System Integrated 700 3 BASE Series 3 28 3758424 Revision B December 2005 ...
Page 48: ...Sealed System Information Integrated 700 3 BASE Series 4 8 3758424 Revision B December 2005 ...
Page 52: ...Airflow Fan Blade Spacing Integrated 700 3 BASE Series 5 4 3758424 Revision B December 2005 ...
Page 58: ...Icemaker Information Integrated 700 3 BASE Series 6 6 3758424 Revision B December 2005 ...
Page 114: ...Wire Diagrams Schematics Integrated 700 3 BASE Series 10 10 3758424 Revision B December 2005 ...