7 Teleservice Application Framework
User Manual
215/374
7.3.6.3
Static mode
7.3.6.3.1
Basic DLC file structure
Every datalogger configuration file has the following basic components:
Necessary DLC file objects
Parameter
Description
[JOBOPTIONS]
Start tag of the DLC file
ACTIVE
Active flag will be automatically set to 1 by ylogd after correct file parsing
LFJNAME
Name of the log file job
LFFORMAT
Format of the data logger file:
1 : ASCII_STD
2 : ASCII_TC1
3 : ASCII_CSV
4 : BINARY_C2C_LE
5 : BINARY_TC3_LE
MEMSIZE
Maximum size of the data logger file in bytes (Maximum value is 500 MB)
BASIC_SAMPLE_TIME
Time interval in which is checked whether the values have changed
TIMESTAMP
Time stamp at the beginning of every new logged line in the data logger
file
[FILEHEADER]
Start tag of the log-file
COMMENT
Comment
[SAMPLECONDITIONS]
Start tag of the values which shall be logged chapter
NUMCONDITIONS
Number of values which shall be logged
[MASTERSAVECONDITIONS]
Start of the chapter for master save conditions.
See also How the logger mechanism works (see "
" on page
NUMMASTERSAVECONDITIONS Number of master save conditions which must be valid before the
"normal" save conditions are checked
[SAVECONDITIONS]
Start of the chapter for save conditions.
See also How the logger mechanism works (see "
" on page
LOG_MECHANISM
Log mechanism modes:
Summary of Contents for TC1
Page 1: ...TC1 User Manual Version of this document V1 00r0 ...
Page 25: ...5 Hardware User Manual 25 374 5 2 2 Block Diagram Variant TC1 WIFI ...
Page 34: ...5 Hardware User Manual 34 374 5 6 Housing Connector Top view and side view Bottom View ...
Page 125: ...7 Teleservice Application Framework User Manual 125 374 TAF overview ...
Page 190: ...7 Teleservice Application Framework User Manual 190 374 How the logger mechanism works ...