29
Free-AIr-3-IN
© STULZ SpA – all rights reserved EN/02.2018
Identified Substance
CAS Number
acrylonitrile butadiene styrene terpolymer
9003-56-9
polystyrene homopolymer
9003-53-6
polycarbonatefrom bisphenol A
103598-77-2
10. Technical data and drawings
NOTeS ON TeCHNICAL DATA SHeeTS
* Measured at 2 m distance from t
he unit, free field, working in nominal conditions.
MODeL
FCL700B112Z000
Outside operating limit temp. min/max
°C
-20 / +45
Inside operating limit temp. min/max
°C
20 / 40
Weight
kg
75
Height / Width / Depth
mm
1250 / 600 / 600
Nominal voltage
V
48 DC
Voltage range
V
36÷57 DC
Number / Type of fan
2 / EC radial
Nominal conditions
Nominal air flow
m
3
/h
4500
ESP
Pa
100
External sound pressure level*
db(A)
61
Power consumption at nominal conditions
kW
0,42
Nominal operating current (NOA)
A
9
Max conditions
Max air flow
m
3
/h
5400
Max power consumption
kW
2 x 0,39
Max operating current (MOA)
A
2 x 8