23
Free-AIr-3-IN
© STULZ SpA – all rights reserved EN/02.2018
INFOrMATION
Test procedure can be accessed only with keypad ACTKPDC1010H. 3-digit keypad ACTUKPD
is not useful to this purpose.
In addition to the semi-automatic test, some other electrical measurements are necessary to
exclude any fault on the FCL.
• Start the FCL by pressing the ON-OFF push-button on the display.
• Enter MANUAL CONTROL and arrive to “Time going out from manual control”. Set this time at
least to 5 minutes.
• Then, remaining inside MANUAL CONTROL, arrive to “Fan 1” and “Fan 2” and set fans speed.
• Check power supply voltage.
• Check current absorbed by the fans.
• Restore “Fan 1” and “Fan 2” to 0 and exit MANUAL CONTROL. In any case, C102 will go out from
manual control within the value set for “Time going out from manual control”.
• Check that no alarms appear in standard working conditions.
6.3. Other tests (facultative)
INFOrMATION
To change temperature measured by the probes, heat or cool their bulbs physically or alterate
their offset, please refer to the controller manual. To enable FCL working, free cooling conditions
must be respected: TI – TAE > 2°C in normal conditions and 1°C in emergency mode.
• Change temperature measured by internal probe (S1) and, if needed, temperature measured by
external probe (S2) to have free cooling conditions. Verify at different internal temperatures if
working logic is according to working diagrams on controller manual.
• Check emergency mode and high temperature alarm, increasing temperature measured by
internal temperature probe above E0401 (threshold of emergency mode) and B03 (threshold of
high temperature alarm - please consider the delay of 10 s for this alarm).
ATTeNTION
After that, restore all offsets to 0.
6.4. Shutdown
To shut the unit down disconnect it from all its power supplies using the related isolating switches.
DANGer
The ON-OFF key on the C102 display is only used to put the unit in stand-by. It must not be
thought to be a safety component to turn the unit off prior to performing maintenance.