Installation
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A-
7.4.
Connecting water supply line(s)
CAUTION
Frost protection.
Protect the entire system from frost.
IMPORTANT
CAUTION
Contaminated water pipes.
Filings and dirt must not get into water pipes!
●
All pipes must be cleaned before they are connected to the unit.
IMPORTANT
CAUTION
Resistant materials.
The connection between the demineralization system and the humidifier must consist of a material that
is resistant to demineralized water.
●
Only use approved materials. See "4.7. Application limits" on page 20.
IMPORTANT
CAUTION
Regulations from water supply companies.
Regulations from water supply companies must be complied with.
WARNING
For the ultrasonic humidifier, use demineralized drinking water with the conductivity that is suitable for
your application (see section "4.7. Application limits" on page 18).
Provide each unit with a stop cock in the drinking water supply pipe.
Clean all lines before connecting them to the humidifier. The supply line can be a pressure hose or a
stainless steel tube, depending on the safety risk.
Connect the overflow pipe for additional security. However, no water flows into the overflow during nor
-
mal operation.
CAUTION
Demineralized drinking water.
The ultrasonic humidifier is operated with demineralized drinking water, to ensure that the transducers
retain their function throughout the unit's service life. Furthermore, if the mineral content of the water is
too high for the planned application, this may lead to the formation of deposits in the humidified room.
●
Check the mineral content and conductivity of the drinking water to prevent damage to property.
●
Replenish ion exchangers regularly and in good time.
IMPORTANT