SBM-01 high precision battery monitor
18
The super-lock must not be confused with the setup-lock (Function F20).
The big difference between the two is that anybody can disable the
setup-lock, even without communication between SBM-01 and PC. The
setup-lock is used to avoid accidental altering of the Function values.
While the super-lock can only be (de-)activated via the PC-link using a
unique password. The super-lock feature is primarily meant for warranty
purposes.
5. TROUBLESHOOTING GUIDELINE
PROBLEM
REMEDY OR SUGGESTION
The monitor doesn’t operate (no
display)
- Check monitor- and battery
side
connections.
- Make sure the inline fuses are
installed and not blown.
- Check battery voltage. Battery
might be flat. Vbatt must be
>
8VDC.
- Try to restart the monitor by
removing/placing the fuses
again.
Current readout gives wrong
polarity (positive current instead
of negative when discharging)
- Current sense leads from the
shunt are reversed. Check the
installation
guide.
The monitor resets all the time
- Check the wiring for corrosion
and/or loose contacts.
- Battery might be flat or
defective.
No changes can be made in the
setup-mode
- Check if the setup-lock is
OFF
(Function
F20)
- Your SBM-01 might be
locked by the super- lock. Ask
the installer for the password to
unlock the monitor using the
PC-link.
Not all readouts in normal mode
can be selected
- Installer has cancelled some
parameter readouts using the
administrator
software
with the
PC-link.
‘CHARGE BATTERY’ or
- Charge battery full