OPERATING

BULK phase (constant current) - 

The batteries need more current than the battery charger

can supply. Current is limited to the maximum rated output. The battery charger can enter this
phase during start-up, when the batteries are low or when a high load is connected.

ABSORPTION phase (constant voltage) - 

The battery charger charges the batteries at a con-

stant ABSORPTION voltage and at the current they need.
The current needed by the batteries will tend to diminish over time. When the required current
is less than 20% of the maximum output value, the charger will change to the FLOAT phase.

FLOAT phase (maintenance) - 

The battery charger charges the batteries at the constant

FLOAT voltage. In this phase, as the batteries reach maximum capacity, they will tend to absorb
current close to zero Ampere. This FLOAT phase will allow the batteries to be on charge with-
out the risk of overloading. The next step to the ABSORPTION phase occurs when the demand
for current goes over 20% of the maximum output value.

HALF-POWER MODE

If the supply voltage of the equipment drops under 97 Vac the battery charger will activate the
“half power” mode. In this mode the battery charger can supply, a maximum value half of the
maximum nominal output current. In this way you can reduce the current absorption from the
AC supply. This feature is useful when the battery charger is supplied via a generator or from a
dock outlet with limited power output.
The half power mode can be activated manually by using the remote LCD terminal (optional).

CHARGING CHARACTERISTICS

Charging occurs in 3 phases:

OPERATION

When the battery charger is switched on for a short period, all the LEDS on the front panel will
light up. After that the battery charger will place itself in the optimum charging mode to best suit
the batteries or load connected. The battery charger has a loading characteristic of the IUoU type.
The MBC battery chargers can also be used as a power supply, that is, with batteries discon-
nected.
We suggest you use the battery charger in this mode only occasionally and not for ordinary
use. However, avoid connecting high inductive loads (e.g. high powered motors) with the bat-
teries disconnected as it you could cause damage to the equipment, even if rare to happen.

(V)

14.1 (28.2) [Gel 14.4 (28.8)]

(I)

Imax

20% Imax

BULK

ABSORPTION

FLOAT

NEW CYCLE

TIME

TIME

13.5 (27.0) [Gel 13.8 (27.6)]

Summary of Contents for Innotec MBC 12-25/3

Page 1: ...c 13 5 13 8 13 5 13 8 13 5 13 8 13 5 13 8 13 5 13 8 13 5 13 8 Output Amp 8 12 25 30 40 60 Cooling Natural Fan Fan Fan Fan Fan Outputs 2 2 3 3 3 3 Frequency 45 66 Hz 45 66 Hz 45 66 Hz 45 66 Hz 45 66 Hz 45 66 Hz PFC Ambient temp range 20 to 70 C 20 to 70 C 20 to 70 C 20 to 70 C 20 to 70 C 20 to 70 C Dimensions lxwxh mm 155x205x75 155x205x75 155x268x75 272x334x127 272x334x127 272x412x127 Weight kg 1 ...

Page 2: ...Pag 1 MBC 12 08 2 12 12 2 12 25 3 24 12 2 INDEX Pag 13 MBC 12 30 3 12 40 3 12 60 3 24 30 3 Pag 29 MBC 12 80 3 24 60 3 24 80 3 ...

Page 3: ...REV 000 User s Manual MBC BATTERY CHARGER MBC BATTERY CHARGER MBC 12 08 2 MBC 12 12 2 MBC 12 25 3 MBC 24 12 2 GB 1 ...

Page 4: ...on Pag 5 Installation voltage supply batteries Pag 6 Installation Selecting the charging method Pag 7 Operation Control signal Pag 8 Ope characteristics ration Charging Pag 9 Operation Control panel Maintenance Pag 10 Technical data INDEX GB ...

Page 5: ...MS Compatible with every kind of generator Short circuit overloading output overvoltage and overheating protection Can work in a wide range of ambient temperatures INSTALLATION BEFORE USING THE BATTERY CHARGER CAREFULLY READ THIS USER S MANUAL IN CASE OF DOUBT CONTACT THE STUDER INNOTEC SUPPLIER OR AFTER SALES SERVICE DEPARTMENT THE BATTERY CHARGERS HAS BEEN DESIGNED FOR FIXED INSTALLATIONS FOR IN...

Page 6: ...ery charger except the base must be kept at a distance from walls or objects by a minimum of 5 cm FIG 1 The cables connected to the output terminals have a maximum length of 4 metres WARNING the battery charger must be used only with a re chargeable lead liquid electrolytic batteries or lead gel sealed or non sealed WARNING the outer surface of the battery charger is used as a heat sink therefore ...

Page 7: ...connections to an AC supply see fig 2 Before powering up the battery charger check that the power supply voltage described on the rating label corresponds to that supplied by the AC supply source In the electrical circuit a two pole switch must be installed for the sole use of switching the equip ment ON OFF The insulation between the contact points of the connections of the AC supply must be at l...

Page 8: ...gthen the char ging time FIG 3 a If the installation has only one or two groups of batteries always connect the output marked MAS TER This is the main outlet of the battery charger If the MASTER is not connected the battery charger may supply an output voltage lower than rated It is advisable to connect the group of batteries which are used more often typically the service group to the MASTER outp...

Page 9: ...present positive SLAVE B output 650mA max By drawing 100mA the error is less than 0 7 Basic state of battery charger 20 mA max Battery charger total current positive shunt 10 mA max The transduction ratio is 100mV 100A GND signal 1 V master GND signal 2 V slave A GND signal 3 V slave B if it present Battery charger total current negative shunt Connection PIN 4 HIGH IMPEDENCE V CHARGE State OFF or ...

Page 10: ...AT phase FLOAT phase maintenance The battery charger charges the batteries at the constant FLOAT volt age In this phase as the batteries reach maximum capacity they will tend to absorb current close to zero Ampere This FLOAT phase will allow the batteries to be on charge without the risk of overload ing The next step to the ABSORPTION phase occurs when the demand for current goes over 20 of the ma...

Page 11: ...in output Check output cables the group of batteries and the points of use connected to the battery charger LED Status Description LED Color Off No mains power or overheating In case of overheating check if the installation of the battery charger is correct Switch off and allow the equipment to cool down for at least 10 minutes Power ON Green Description Off Green Green Off Fixed Flashing CHARGE L...

Page 12: ... Cycoloy Anodized OR5066 155 x 205 x 75 mm 155 x 268 x 75 mm 1 3 Kg 1 4 Kg 2 3 Kg INPUT CHARACTERISTICS PROTECTION Supply voltage 4 Frequency Maximum absorption 230 Vac 6 Maximum absorption 115 Vac 6 CASE Material Colour Dimensions WxHxD Weight Reverse polarity 7 Overload Output short circuit Overheating AMBIENT CHARACTERISTICS Operating temperature Cooling Humidity GENERAL Connector for remote pa...

Page 13: ...205 181 90 135 155 75 MBC BATTERY CHARGER DIMENSIONS mm 12 08 2 12 12 2 11 ...

Page 14: ...12 268 244 90 135 155 75 MBC BATTERY CHARGER DIMENSIONS mm 12 25 3 24 12 2 ...

Page 15: ...REV 001 MBC BATTERY CHARGER MBC 12 30 3 MBC 12 40 3 MBC 12 60 3 MBC 24 30 3 User s Manual MBC BATTERY CHARGER GB 13 ...

Page 16: ... batteries Pag 18 Installation Selecting the charging method Pag 19 Operation Control signal Pag 20 Operation Charging characteristics Pag 21 Operation Control panel Pag 22 23 Notification signs Pag 24 25 Programming the battery charger Pag 26 Maintenance Technical data INDEX GB ...

Page 17: ...V RMS Universal AC supply input 280 83 Vac 45 66 Hz Power factor cos ϕ equal to 1 Compatible with every kind of generator Short circuit overloading output overvoltage and overheating protection Can work in a wide range of ambient temperatures Variable speed for the cooling fan High technology control panel Automatic and manual half power mode CAN BUS interface for data transfer Case constructed in...

Page 18: ...ool the equipment The perimeter of the battery charger except the base must be kept at a distance from walls or objects by a minimum of 5 cm CHARACTERISTICS AND INSTALLATION GB The cables connected to the output terminals have a maximum length of 4 metres WARNING the battery charger must be used only with a re chargeable lead liquid electrolytic batteries or lead gel sealed or non sealed 16 FIG 1 ...

Page 19: ...fore powering up the battery charger check that the power supply voltage de scribed on the rating label corresponds to that supplied by the AC supply source In the electrical circuit a two pole switch must be installed for the sole use of switching the equipment ON OFF The insulation between the contact points of the connections of the AC supply must be at least 3 mm The connections to the AC supp...

Page 20: ...ry charger may supply an output lower voltage than rated and therefore less power It is advisable to connect the group of batteries which are used more often typically the ser vice group to the MASTER output terminal The positive output terminals that are not used must be kept free do not bridge the terminals WARNING the use of inadequate size cables and the incorrect connection of terminals or el...

Page 21: ...nterface connection CANH and CANL signals use an unscreened cable with a twisted pair cross section 0 25 0 35 mm2 AWG 22 24 impedance 100 150 ohm The maximum total length of the data signal cable should be no more than 100 m Activate the terminator at the first and last device connected to the network If there is only one device the terminator does not need to be activated An example of a network ...

Page 22: ...r 97 Vac the battery charger will activate the half power mode In this mode the battery charger can supply a maximum value half of the maximum nominal output current In this way you can reduce the current absorption from the AC supply This feature is useful when the battery charger is supplied via a generator or from a dock outlet with limited power output The half power mode can be activated manu...

Page 23: ...ange Green LED Colour OFF Red Description No problem with manual reset Problem with manual reset see error codes The information supplied by the LEDS are listed as below POWER LED LED colour OFF Green Flashing Description No mains power Power ON Battery charger in stand by mode ON STAND BY BUTTON Use this button to put the battery charger in stand by mode To activate this mode simply press the but...

Page 24: ...hich caused the problem is no longer present If this message appears frequently check whether the battery charger has been installed properly The temperature measured by the battery sensors optional is outside the range determined for the charge 20 55 C The output voltage of the battery charger becomes 12 8V 25 6V in the 24V models so that the batteries are not damaged This message disappears when...

Page 25: ...era tion Check whether the battery charger has been installed properly Turn off the equipment and leave it to cool down for at least 10 minutes The letter E and the number appear flashing on the display alternately Prolonged overload The battery charger has delivered maximum current at a voltage lower than half the nominal output value for too long Check the output wiring the group of batteries an...

Page 26: ...ion is made this could reduce the service life of the batteries or mean the charging time takes longer The letter liquid Electrolyte or gel will appear flashing on the display according to the current setting To change the setting press the key quickly press and release the button in less than 1 second To make the setting operative press the key for at least 2 seconds The display will confirm the ...

Page 27: ...ing operative press the key for at least 2 seconds The display will confirm the setting by showing the number selected for one second steady Once the programming procedure has been completed the following symbol will be shown for 1 second ACTIVATING INACTIVATING THE MONITOR MODE This function enables the user to activate or inactivate the battery charger s monitor mode If it is activated the monit...

Page 28: ...Kg 5 4 kg INPUT CHARACTERISTICS PROTECTION Supply voltage Frequency Maximum absorption 230 Vac 4 Maximum absorption 115 Vac 4 Power factor cos ϕ CASE Material Colour Dimensions WxHxD Weight Reverse polarity 5 Overload Output short circuit Overvoltage in output 6 Overheating Battery overtemperature AMBIENT CHARACTERISTICS Operating temperature Cooling Humidity GENERAL Connector for remote panel Saf...

Page 29: ...280 334 272 220 127 MBC BATTERY CHARGER DIMENSIONS mm 12 30 3 12 40 3 27 ...

Page 30: ...28 358 412 272 220 127 MBC BATTERY CHARGER DIMENSIONS mm 12 60 3 24 30 3 ...

Page 31: ...REV 000 User s Manual MBC BATTERY CHARGER GB MBC BATTERY CHARGER MBC 12 80 3 MBC 24 60 3 MBC 24 80 3 29 ...

Page 32: ...ply batteries Pag 32 Installation Selecting the charging method Pag 33 Operation Control signal Pag 35 Operation Charging characteristics Pag 36 Operation Control panel Pag 37 38 Notification signs Pag 39 40 Battery charger programming Pag 41 Maintenance Technical data INDEX GB ...

Page 33: ...mV RMS Universal AC supply input only MBC 12 80 8 Power factor cos ϕ equal to 1 Compatible with every kind of generator Short circuit overloading output overvoltage and overheating protection Can work in a wide range of ambient temperatures Variable speed for the cooling fan High technology control panel Automatic and manual half power mode CAN BUS interface for data transfer Case constructed in s...

Page 34: ...heat helps to cool the equipment The perimeter of the battery charger except the base must be kept at a distance from walls or objects by a minimum of 5 cm CHARACTERISTICS AND INSTALLATION GB The cables connected to the output terminals have a maximum length of 4 metres WARNING the battery charger must be used only with a re chargeable lead liquid electrolytic batteries or lead gel sealed or non s...

Page 35: ...fore powering up the battery charger check that the power supply voltage de scribed on the rating label corresponds to that supplied by the AC supply source In the electrical circuit a two pole switch must be installed for the sole use of switching the equipment ON OFF The insulation between the contact points of the connections of the AC supply must be at least 3 mm The connections to the AC supp...

Page 36: ...ry charger may supply an output lower voltage than rated and therefore less power It is advisable to connect the group of batteries which are used more often typically the ser vice group to the MASTER output terminal The positive output terminals that are not used must be kept free do not bridge the terminals WARNING the use of inadequate size cables and the incorrect connection of terminals or el...

Page 37: ... data interface connection CANH and CANL signals use an unscreened cable with a twisted pair cross section 0 25 0 35 mm2 AWG 22 24 impedance 100 150 ohm The maximum total length of the data signal cable should be no more than 100 m Activate the terminator at the first and last device connected to the network If there is only one device the terminator does not need to be activated An example of a n...

Page 38: ...r 97 Vac the battery charger will activate the half power mode In this mode the battery charger can supply a maximum value half of the maximum nominal output current In this way you can reduce the current absorption from the AC supply This feature is useful when the battery charger is supplied via a generator or from a dock outlet with limited power output The half power mode can be activated manu...

Page 39: ...ange Green LED Colour OFF Red Description No problem with manual reset Problem with manual reset see error codes The information supplied by the LEDS are listed as below POWER LED LED colour OFF Green Flashing Description No mains power Power ON Battery charger in stand by mode ON STAND BY BUTTON Use this button to put the battery charger in stand by mode To activate this mode simply press the but...

Page 40: ...hich caused the problem is no longer present If this message appears frequently check whether the battery charger has been installed properly The temperature measured by the battery sensors optional is outside the range determined for the charge 20 55 C The output voltage of the battery charger becomes 12 8V 25 6V in the 24V models so that the batteries are not damaged This message disappears when...

Page 41: ...ther the battery charger has been installed properly Turn off the equipment and leave it to cool down for at least 10 minutes The letter E and the number appear flashing on the display alternately Prolonged overload The battery charger has delivered maximum current at a voltage lower than half the nominal output value for too long Check the output wiring the group of batteries and the load connect...

Page 42: ... selec tion is made this could reduce the service life of the batteries or mean the charging time takes longer The letter liquid Electrolyte or gel will appear flashing on the display according to the current setting To change the setting press the key quickly press and release the button in less than 1 second To make the setting operative press the key for at least 2 seconds The display will conf...

Page 43: ...ing operative press the key for at least 2 seconds The display will confirm the setting by showing the number selected for one second steady Once the programming procedure has been completed the following symbol will be shown for 1 second ACTIVATING INACTIVATING THE MONITOR MODE This function enables the user to activate or inactivate the battery charger s monitor mode If it is activated the monit...

Page 44: ...ISTICS Maximum output current 1 Charge absorption voltage Charge float voltage Residual ripple 2 Charging characteristics Number of outputs 3 80 A 60 A 80 A 14 1 Vdc 14 4 Vdc GEL 28 2 Vdc 28 7 Vdc GEL 13 5 Vdc 13 8 Vdc GEL 27 0 Vdc 27 5 Vdc GEL 90mV RMS max Automatica a tre stadi IUoU 3 Yes through fuse Yes Yes Yes Yes Yes optional 83 280 Vac with power 150 280 Vac with power reduction under 195 V...

Page 45: ...447 495 272 220 127 12 80 3 24 60 3 24 80 3 43 MBC BATTERY CHARGER DIMENSIONS mm ...

Page 46: ...STUDER INNOTEC RUE DES CASERNES 57 1950 SION SWITZERLAND TEL 41 0 27 205 60 80 FAX 41 0 27 205 60 88 www studer inno com E mail info studer inno com ...

Reviews: