46
10.4.5 S
YSTEM
P
ARAMETER
–
P.
There is a total of 23 parameters within the system parameter.
Each parameter is listed in the below table along with what they are set to as standard.
Index Description
Range
S-FX 70
S-FX 125
S-FX 220
S-FX 320
P.01
Heat Demand
Selection
0 = Either room thermostats
can be used to operate boiler.
1 = Both room thermostats
need to be closed to operate
boiler.
2 = 0-10v on Temperature
3 = 0-10v on Power
4 = Both room thermostats are
used on 2 separate zones.
5 = Both room thermostats are
used on 2 separate zones with
outside sensor.
0
0
0
0
P.02
Select Cascade
Sensor
0 = Disabled
1 or 2 = Enabled
0
0
0
0
P.03
No Function
-
-
-
-
-
P.04
3 Way Valve Time 0
– 255 Seconds
0
0
0
0
P.05
Activation Timer*
0
– 255 Seconds
1
1
1
1
P.06
Deactivation
Time*
0
– 255 Seconds
5
5
5
5
P.07
Activation Heat
Output*
0
– 100%
70%
70%
70%
70%
P.08
Deactivation Heat
Output*
0
– 95%
5%
5%
5%
5%
P.09
Low Loss Header
Function
0 = Disabled
1 = Enabled
0
0
0
0
P.10
Fill System
Function
0 = Disabled
1 = Enabled
0
0
0
0
P.11
Select 3 Way
Valve
0 = 2 or 3 Wire
1 = 3 Wire
0
0
0
0
P.12
0-10v On Temp
Off Voltage**
0-10v
2.5v
2.5v
2.5v
2.5v
P.13
0-10v On Temp
On Voltage**
0-10v
3.0v
3.0v
3.0v
3.0v
P.14
0-10v On Temp
Max Voltage **
0-10v
10.0v
10.0v
10.0v
10.0v
P.15
0-10v On Temp
Min Temp**
0-100c
20c
20c
20c
20c
P.16
0-10v On Temp
Max Temp**
0-100c
90c
90c
90c
90c
P.17
0-10v On Power
Off Voltage**
0-10v
2.5v
2.5v
2.5v
2.5v
P.18
0-10v On Power
On Voltage**
0-10v
3.0v
3.0v
3.0v
3.0v
P.19
0-10v On Power
Max Voltage **
0-10v
10.0v
10.0v
10.0v
10.0v
P.20
0-10v On Power
Min Power**
0
– 100%
0%
0%
0%
0%
P.21
0-10v On Power
Max Power**
0
– 100%
100%
100%
100%
100%
P.22
Enable Slave
Boiler DHW (Auto
Cascade)
0 = Disabled
1 = Enabled
0
0
0
0
P.23
Slave Boiler Cont.
Comfort
0 = Disabled
1 = Enabled
0
0
0
0
Notes:
*
These Parameters are only active when two control units are connected to the same ACP01 display.
**These parameters are only active when the system works with a 0
– 10 volt controller.