CONTROLLING OPTIONS AND SETTINGS
11.1 General
The following paragraphs describe some general functions of the boiler and their possible use.
11.1.1
E
XTRA BOILER CONTROL
When all units (cascaded) are firing at their maximum it is possible to start an extra “external” heating source. This
unit can be connected to the “Burner Burning” contacts (connection 21-22).
P5DE
Extra Boiler output enable (1) (display C4)
When this parameter is set 1, the contact “Burner Burning” will close, but only when all units are firing at a certain
(programmable) input percentage. The standard factory setting for this function is “OFF”.
11.1.2
M
AX COOLING TIME
The fan will cool down the heat exchanger according to the temperature settings (parameters) of the software. With
this cooling parameter the maximum run time of the fan can be programmed.
P2LK
Max cooling time (display D4)
This function is not used for central heating boilers.
11.1.3
T
EMPERATURE DISPLAY ON
/
OFF
Selection for showing the measured temperatures at the operation display of the boiler.
P5BJ
Temperature display 1=on (display D5)
The measured temperature at the operation display.
0 = not visible
1 = visible
11.1.4
W
ATER PRESSURE
P4AD
pressure 0=off, 1=sensor, 2=switch.
When the water pressure exceeds 4 bar a pressure switch must be used instead of the sensor (suitable till 4 bar).
With the switch, pressure can go up to 6 bar.
In this case, remove the pressure sensor and replace it by the pressure switch. Now set the parameter at the con-
trol panel by changing “D7 config” from 1 into 2.
11.1.5
G
AS TYPE SELECTION
Settings for gas types: natural gas, propane or butane-propane mixture (B/P).
P4 BD
Gas type (0=standard, 1=propane
,
2=B/P) (display D8)
This parameter is set 0 for the common used gas types such as natural gas G20 or G25.
By setting this parameter 1 for propane, fan speed is reduced.
Set this parameter 2 for B/P.
0 =
standard gas (e.g.: natural gas), Lw, Ls (Lw and Ls only for Poland)
1 =
propane
2 =
B/P
By each setting, the relevant Soft start settings are automatically adjusted, depending on its main setting P4BE,
see next section § 11.1.6.