14.4 Adjusting procedures
Procedures 1 and 2, referred to in the previous sections 14.2 and 14.3, are described here:
Procedure 1: adjust at maximum load
In case
B
(replacement of gas valve or gas conversion): consult § 14.3. before starting procedure 1 below.
Carry out the next 4 steps:
1. Press [SERVICE] button for about 3 seconds.
Display message
H E A T I N G : S e r v i c e
2 6 %
> > >
1 2 3 . 4 ° C ( 1 2 3 . 4 ° C )
Boiler is activated and operates at service mode at 26% (minimum). (example)
2. Press
[▲] button until maximum load is reached:
Display message
H E A T I N G : S e r v i c e
1 0 0 %
> > >
1 2 3 . 4 ° C ( 1 2 3 . 4 ° C )
Boiler is activated and operates at service mode at 100% (maximum). (example)
3. Measure the CO
2
percentage at the flue gas outlet.
4. By setting screw [2], adjust the gas valve to obtain the CO
2
value of table 1.
NOTICE: For the A
+
120, 150 and 180 boilers use only the RIGHT side gas valve for adjusting.
Decrease CO
2
percentage
CO2
[2]
Turn screw [2] right (clockwise)
Increase CO
2
percentage
CO2
[2]
Turn screw [2] left (counter clockwise)
The service operation of the boiler will be active for 40 minutes.
After this period the boiler will return to normal operation.
Procedure 2: adjust at minimum load
In case
B
(gas conversion or replacement of gas valve): consult § 14.3. before starting procedure 2 below.
Carry out the next three steps:
1. Press
[▼] button until minimum load is reached.
Display message
H E A T I N G : S e r v i c e
2 6 %
> > >
1 2 3 . 4 ° C ( 1 2 3 . 4 ° C )
Boiler is activated and operates at service mode at 26% (minimum).
2. Measure the CO
2
percentage at the flue gas outlet.
3. By setting screw [1], adjust the gas valve to obtain the CO
2
value of table 1.
NOTICE: For the S-CB
+
120, 150 and 180 boilers use only the RIGHT side gas valve for adjusting.
Decrease CO
2
percentage
CO2
[1]
Turn screw [1] left (counter clockwise)
Increase CO
2
percentage
CO2
[1]
Turn screw [1] right (clockwise)
The service operation of the boiler will be active for 40 minutes.
After this period the boiler will return to normal operation.