System Specifications
System Specifications
A-5
Table A-2. ftServer 2600, 4500, and 6300 System: CPU-I/O Enclosure Specifications
Power
Input power
700W for each enclosure (1400W total)
Nominal input
voltage
100-127 or 200-240 volts; 50/60 Hz
Power Factor
0.98
VA
720 (240V x 3A)
700 (100V x 7A)
Protective earth
ground current
3.5 mA maximum for each AC power cord
Physical Dimensions
Height
7.0 in. (17.78 cm; 4U)
Width
17.50 in. (44.45 cm)
Depth
29.27 in. (74.34 cm), with modem, excluding rail and bezel
Weight, including
12 DIMMS,
2 processors, and
8 disks per
enclosure
Two enclosures: 84 lb (38.1 kg), fully loaded
Rails and shelf unit: 13.8 lb (6.26 kg)
Environmental
Operating
temperature
41
F to 95
F (5
C to 35
C)
For every 800 ft (243.8 m) above 2000 ft (609.6 m), lower the maximum
operating temperature by 1
C.
Storage temperature
-38
F to 140
F (-40
C to 60
C), vented
Operating altitude
0 ft to 10,000 ft (0m to 3,048m)
Maximum rate of
temperature change
during operation
12
C per hour
Relative humidity
during operation
10% to 80% (noncondensing)
Relative humidity
during storage
5% to 95% (noncondensing)
Heat dissipation,
each system (both
enclosures)
4774 BTUs per hour
Summary of Contents for ftServer 2600
Page 1: ...Stratus Technologies R638 02 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide...
Page 8: ...Tables viii Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Page 48: ...Planning for Cables 3 4 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Page 70: ...Monitor Requirements 6 6 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Page 98: ...Index Index 4 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...