StoneL publication 105410revD
7 AN 70 en
Axiom AN |
9
3
Maintenance, repair and installation
3.1
Maintenance and repair
No routine maintenance of Axiom units is required when installed in environments for which they are designed. If installed in severe
environments, pneumatic components may require replacement at more frequent intervals for maximum performance. Repair of Axiom units
must be done by StoneL or by qualified personnel that are knowledgeable about the installation of electromechanical equipment in hazardous
areas. All parts needed for repair must be purchased through a StoneL authorized distributer to maintain warranty and to ensure the safety and
compliance of the equipment.
3.2 Installation
Attention:
If required, the Axiom housing can be
grounded to earth potential by either the internal or
external ground lug. (See Assembly drawing 1.6 items 4
and 5 on page 4)
Attention:
In order to maintain enclosure type and IP
ratings, cover shall be tightened by hand a minimum of
1/4 turn after cover engages o-ring. Do not use any tool to
tighten the cover.
WARNING
Solenoid power supplied must be limited with a fuse or circuit
breaker rated to 2 Amps maximum.
Field wiring
• It is the responsibility of the installer, or end user, to install this
product in accordance with the National Electrical Code (NFPA 70)
or any other national or regional code defining proper practices.
• This product comes shipped with conduit covers in an effort to
protect the internal components from debris during shipment and
handling. It is the responsibility of the receiving and/or installing
personnel to provide appropriate permanent sealing devices to
prevent the intrusion of debris or moisture when stored or installed
outdoors.
• Use field wiring rated at least 10 K (+10° C) above ambient
temperature.
Attention:
If the unit is used in a manner not specified by
StoneL, the protection provided by it may be impaired.
Caution:
To maintain safety, only power supplies that
provide Double/Reinforced insulation, such as those with
PELV/SELV outputs, shall be used. (As applicable)
3.3
Specific conditions of use
See Declaration of Conformity for specific conditions of use.