7 AN 70 en
20
| Axiom AN
StoneL publication 105410revD
4.2
Valve communication terminals (VCT)
4.2.3
VCT with AS-Interface communication and extended addressing (97S & 97W)
Specifications
Communication protocol
AS-Interface v3.0
Configuration
(2) Discrete inputs (sensors)
(2) Auxiliary discrete inputs
(2) Discrete outputs (solenoid)
Input voltage
26.5-31.6 VDC (AS-I voltage)
Output voltage
24 VDC (+/- 10%)
Quiescent current
35 mA
Current consumption
(coil energized)
56 mA
Maximum output current
100 mA (all outputs combined)
Default address
0A
ID/IO codes
ID = A; IO = 7; ID1 = F; ID2 = E (S-7.A.E.)
Bit assignment
Inputs
Bit 0 = red LED / valve closed
Bit 1 = green LED / valve open
Bit 2 = aux input 1
Bit 3 = aux input 2
Outputs
Bit 0 = OUT 1
Bit 1 = OUT 2
Bit 2 = wireless link enabled
Bit 3 = not available
Parameter
Bit 0 = wink
Bit 1-3 = not used
Common receptacle options pin-out
Wiring diagram
3 wire R
TN
Aux IN2 -
Solenoid 1
Power
AS-i/FAULT
Manual
Solenoid 2
Power
SET
OPEN
SET
CLOSED
Aux IN1 -
Aux IN +
ASi -
ASi +
ASi -
ASi +
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
Setup Instructions:
Operate actuator to closed
position and touch SET CLOSED
for 2 seconds.
Operate actuator to open position
and touch SET OPEN for 2 seconds.
SOL2 OUT
+
12
11
-
SOL1 OUT
+
10
9
-
Signal
ASi +
MALE (PINS)
1
2
4
3
MALE (PINS)
2
4
1
3
4-PIN MICRO CONNECTOR (M12)
4-PIN MINI CONNECTOR
not used
ASi -
not used
Pin
1
2
3
4