7 AN 70 en
16
| Axiom AN
StoneL publication 105410revD
Signal
Shield
MALE (PINS)
MALE (PINS)
1
1
2
2
5
5
4
4
3
3
5-PIN MICRO CONNECTOR (M12)
5-PIN MINI CONNECTOR
V +
V -
CAN H
CAN L
Pin
1
2
3
4
5
4.2
Valve communication terminals (VCT)
4.2.1
VCT with DeviceNet™ communication (92S & 92W)
Specifications
Communication protocol
DeviceNet™
Configuration
(2) Discrete inputs (sensors)
(1) Auxiliary analog input (4-20 mA)
(2) Discrete outputs (solenoids)
Input voltage
11 - 25 VDC via DeviceNet™ network
Output voltage
24 VDC
Analog input impedance
254 ohms
Quiescent current
No analog input, no outputs energized:
35 mA @ 24 VDC; 57 mA @ 11 VDC
Current consumption
(coil energized)
56 mA @ 24 VDC
Maximum output current
150 mA (all outputs combined)
Default address
63 (software assigned)
Default baud rate
125K (software selectable 125K, 250K or 500K baud)
Messaging
Polling, cyclic and change of state
DeviceNet™ type
100
Bit mapping
Inputs (3 bytes)
Byte 0, bit 0 = red LED / valve closed
Byte 0, bit 1 = green LED / valve open
Byte 0, bit 7 = fault bit
Byte 1, bits 8-15 = 4-20 mA analog input
Byte 2, bits 16-23 = 4-20 mA analog input
(4-20 mA analog input 0-10,000 scaling)
Outputs (1 byte)
Byte 0, bit 0 = solenoid 1
Byte 0, bit 1 = solenoid 2
Byte 0, bit 2 = wink
Byte 0, bit 3 = remote set closed
Byte 0, bit 4 = remote set open
Byte 0, bit 7 = wireless link enabled
not used
Ain -
Solenoid 1
Power
Module/Network
Status
Manual
Solenoid 2
Power
SET
OPEN
SET
CLOSED
Ain +
V -
CAN L
S H
CAN H
V +
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
Setup Instructions:
Operate actuator to closed
position and touch SET CLOSED
for 2 seconds.
Operate actuator to open position
and touch SET OPEN for 2 seconds.
SOL2 OUT
+
12
11
-
SOL1 OUT
+
10
9
-
Wiring diagrams
Common receptacle options pin-out