7 AN 70 en
10
| Axiom AN
StoneL publication 105410revD
4
Function specific details
4.1
Sensor/switching modules
4.1.1
SST N.O. sensor (35S & 35W)
Specifications
Configuration
(2) N.O. 2-wire solid state sensors
Voltage range
20 - 250 VAC 50/60 Hz; 20 - 125 VDC
20 - 60 VAC 50/60 Hz; 20 - 55 VDC
(with connector
option 18)
Minimum on current
2.0 mA
Maximum continuous current
0.1 amps
Maximum leakage current
0.50 mA (AN35S); 0.60 mA (AN35W)
Maximum voltage drop
6.5 volts @ 10 mA
7.2 volts @ 100 mA
Circuit protection
Protected against short circuits and direct
application of voltage with no load.
Wiring diagrams
SOL
1 PWR 1
SOL
1 PWR 2
Solenoid 1
Power
Open
Closed
Manual
Solenoid 2
Power
SET
OPEN
SET
CLOSED
OPEN NO
OPEN C
CLOSED NO
CLOSED C
SOL
2 PWR 1
SOL
2 PWR 2
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
Setup Instructions:
Operate actuator to closed
position and touch SET CLOSED
for 2 seconds.
Operate actuator to open position
and touch SET OPEN for 2 seconds.
SOL2 OUT
1
12
11
2
SOL1 OUT
1
10
9
2
Common receptacle options pin-out for single coil unit
Common receptacle options pin-out for dual coil unit
Signal
OPEN/CLOSED C
MALE (PINS)
MALE (PINS)
1
1
2
2
5
5
4
4
3
3
5-PIN MICRO CONNECTOR (M12)
5-PIN MINI CONNECTOR
CLOSED NO
OPEN NO
SOL PWR IN +
SOL PWR IN -
Pin
1
2
3
4
5
Signal
OPEN/CLOSED C
MALE (PINS)
MALE (PINS)
1
1
2
2
5
6
4
5
3
4
3
6-PIN MICRO CONNECTOR (M12)
6-PIN MINI CONNECTOR
CLOSED NO
OPEN NO
SOL1 & SOL2 PWR IN
SOL1 PWR IN
Pin
1
2
3
4
5
SOL2 PWR IN
6
6