![Stober SD6 Series Manual Download Page 45](http://html.mh-extra.com/html/stober/sd6-series/sd6-series_manual_1381243045.webp)
ID 442426.04
45
WE KEEP THINGS MOVING
Technical data
4
Manual SD6
4.8
Terminal modules
4.8.1
Specification - XI6
X100 specification
X101 specification
General specification
Maximum cable
length
30 m, shielded
Electrical data
Analog inputs
AE1 and AE2
Level
±10 V
Resolution 16
bits
Internal resistance
> 40 k
Ω
Refresh rate
Cycle time of the
application
Analog input
AE1 as current input
(AE1+ and AE1 shunt
bridged)
Level
±20 mA
Resolution
IO6: 12 bits
XI6, RI6: 16 bits
Internal resistance
492
Ω
Wire break monitoring
Parametrizable in
F15
Analog outputs
AA1 and AA2
Level
±10 V
Maximum output current XI6: 10 mA
IO6, RI6: ± 20 mA
General specification
Maximum cable
length
30 m, shielded
Electrical data
Binary inputs
BE1 to BE3
Low level
0–8 V
High level
12–30 V
Input voltage
Max. 30 V
Input current
Max. 16 mA
Input frequency
Max. 10 kHz
Binary inputs
BE4 and BE5
Low level
0–8 V
High level
12–30 V
Input voltage
Max. 30 V
Input current
Max. 16 mA
Input frequency
XI6: max. 100 kHz
IO6, RI6: max. 250 kHz
Binary outputs
BA1 and BA2
Maximum output current XI6: 50 mA
IO6, RI6: 100 mA
Typical voltage drop
< 2 V
Refresh rate
Cycle time of the
application (at least 1
ms)
Output frequency
Max. 250 kHz
24 vdc power supply
Input voltage
18–28.8 V