6 | Technical data
02/2019 | ID 442728.05
71
6.10
Choke
Technical specifications for suitable chokes can be found in the following chapters.
6.10.1
TEP output choke
are required for drive controllers of sizes 0 to 2 and for a cable length of 50 m or
longer in order to reduce interference pulses and protect the drive system.
Information
The following technical data only applies to a rotating magnetic field frequency of 200 Hz. For
example, this rotating magnetic field frequency is achieved with a motor with 4 pole pairs and a
nominal speed of 3000 rpm. Always observe the specified derating for higher rotating magnetic
field frequencies. Also observe the relationship with the clock frequency.
Properties
Specification
TEP3720-0ES41
TEP3820-0CS41
TEP4020-0RS41
ID No.
53188
53189
53190
Voltage range
3 × 0 to 480 V
AC
Frequency range
0 – 200 Hz
Nominal current I
N,MF
at 4 kHz
4 A
17.5 A
38 A
Nominal current I
N,MF
at 8 kHz
3.3 A
15.2 A
30.4 A
Max. permitted motor
cable length with
output choke
100 m
Max. surrounding
temperature ϑ
amb,max
40 °C
Protection class
IP00
Winding losses
11 W
29 W
61 W
Iron losses
25 W
16 W
33 W
Connection
Screw terminal
Max. conductor cross-section
10 mm²
UL Recognized
Component (CAN; USA)
Yes
Test symbols
Tab. 71: Specification for TEP
Project configuration
Select the output chokes in accordance with the nominal currents of the output chokes, motor
and drive controller. In particular, observe the derating of the output choke for rotating magnetic
field frequencies higher than 200 Hz. You can calculate the rotating magnetic field frequency for
your drive with the following formula:
N
N
p
f
n
60
´
=