13.3.27 71:Firmware
Triggering
Level
Response
Fault counter
A firmware error was detected.
Fault
Causes 1 and 2 only occur when the device starts so that
the inverter can not be enabled. Cause 3 can also occur
during operation.
Z71
Cause
Description
Measure
Acknowledgement
1:FW defective
Only for SDS 5000: An active firmware
error was detected or faulty firmware
was detected in the firmware download
memory.
Reload the firmware using the
POSITool software. Also note the
Service section.
Switch device off/on
2:Activate FW!
Only for SDS 5000: The firmware was
loaded into the inverter but not yet
activated.
Activate the firmware and perform a
device restart. Also note the Service
section.
3:CRC error
A firmware error was detected.
Switch off the 24 vdc power supply and
switch it on again. If the error occurs
repeatedly, replace the inverter.