Concept
ID 442181.07
12
Operating manual ASP 5001
3
WE KEEP THINGS MOVING
3.2
2. Switchoff distance
The 2nd switchoff distance is realized with the ASP 5001. A positively driven safety relay is integrated on the
ASP 5001.
In order for the power output stage of the inverter to be controlled by the control part, the STO safety function
must be deselected at terminal X12.3.
The switching state of the ASP 5001 is acknowledged via the NC contact at terminals X12.1 and X12.2. If the
STO safety function is deselected, the contact is opened. If the ASP 5001 is not controlled, the contact is
closed and the safety function is requested.
3.3
Overall functionality
Note that the following parameters can affect the safety function:
•
A39 Tmax Fast Stop
•
A43 Enable Switchoff Delay
•
A44 Enable Quick Stop
•
A55 Manual Function Button
•
A60 Additional Enable Source
•
The
F61 BA1 Source
to
F70 BA10 Source
parameters
Observe these when configuring, commissioning and modifying your project.
Make sure
•
that the setting of the parameters matches your application.
•
so that the desired overall functionality is achieved after commissioning and each modification.
Information
Note that the ASP 5001 is optional for sizes 0, 1 and 2. The accessories may only be installed and
repaired by STÖBER ANTRIEBSTECHNIK. For this reason, order the inverter with the ASP 5001
installed for these sizes.
For size 3, the ASP 5001 is installed as standard.