Stingray T3000 Series Installation & Maintenance Manual Download Page 1

5330 East 25th Street 

Indianapolis Indiana 46218

Phone: (888) 445-4142

www.tepid.com

Installation &

Maintenance Manual

Certified to ANSI Z358.1

Stingray Systems

SERIES T3000

Floor Mounted 

Emergency Shower

In order to comply with the ANSI Z358.1 Standard the 
following notes should be observed:

•  Station should be assembled and installed in accordance 

with the manufacturer’s instructions, including flushing fluid 
delivery requirements.

•  Station should be in accessible locations that require no more 

than 10 seconds to reach. The shower station shall be located 
on the same level as the hazard and the path of travel shall be 
free of obstructions that may inhibit its immediate use.

•  Station should be located in an area 

identified with a highly visible sign 
positioned so the sign shall be visible 
within the area served by the station. The 
area around the station shall be well lit.

•  Shower shall be positioned so that the showerhead is not 

less than 82 inches (208.3 cm) nor more than 84 inches 
(213.4 cm) from surface on which user stands.

•  Shower spray pattern shall have a minimum unobstructed 

diameter of 20 inches (50.8 cm) at 60 inches (152.4 cm) 
above surface on which user stands, and center of spray 
pattern shall be located at least 16 inches (40.6 cm) from 
any obstruction.

•  If shut off valves are installed in the supply line for 

maintenance purposes, provisions shall be made to 
prevent unauthorized shut off.

•  Refer to ANSI Z358.1 to ensure compliance.

NOTES: It is recommended to flush pipes prior to installing 
shower fixture. Instructions should be reviewed prior to starting 
the installation. Remove parts from packaging and verify all 
necessary parts are accounted for and not damaged.  Please 
contact Stingray Systems for any missing or damaged parts 
prior to starting installation.

Stingray Systems recommends that you work safely at all 
times and in a manner consistent with the OSHA Lock/Tagout 
standard, 29 CFR 1910.147 and other applicable standards.

Summary of Contents for T3000 Series

Page 1: ...lit Shower shall be positioned so that the showerhead is not less than 82 inches 208 3 cm nor more than 84 inches 213 4 cm from surface on which user stands Shower spray pattern shall have a minimum unobstructed diameter of 20 inches 50 8 cm at 60 inches 152 4 cm above surface on which user stands and center of spray pattern shall be located at least 16 inches 40 6 cm from any obstruction If shut ...

Page 2: ...l floor anchors not included into the floor Secure partially assembled unit to the floor with the anchors 5 Thread Shower Head to the station 6 Attach Drench Pull Handle by placing Nylon Washer on each side of outer hole on shower activator arm Insert Drench Pull Handle through hole Lock into place by inserting Cotter Pins into holes of Drench Pull 7 Mount sign near or onto the assembled unit at t...

Page 3: ...least a 20 degree difference between hot water and set temperatures as well as cold water and set temperatures Inspect checks for debris clean replace if needed Remove thermostat and check for debris Make sure liner can move Clean thermostat If continues replace thermostat No cold water Ensure hot connects to hot side cold to cold side Inspect checks for debris clean replace if needed Remove therm...

Page 4: ...ber December Plumbed emergency eyewashes eye face washes drench hoses shower and combinations systems shall be activated and tested for a period long enough to verify operation and ensure that flushing fluid is available WARNING This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm Installer California law requires that this w...