background image

Series SV160

Emergency Shower Valve

(1)

Installation &

Maintenance Manual

M ESV H

Setting the Mixing Valve

Caution:

 When maintaining and adjusting the 

mixing valve, all fixtures should be isolated from 

use.     Stingray Systems recommends that you 

work safely at all times and in a manner consistent 

with the OSHA Lock/Tagout standard, 29 CFR 

1910.147 and other applicable standards.

This mixing valve has been set at the factory to 

deliver 85°F outlet flow. Should the valve require 

adjustment, or an application require a different set 

temperature, proceed as follows:
1.  Contact the proper medical and safety authori-

ties to determine correct water temperature for 

the specific application.

2.  If the valve is outfitted with a padlock #1 and 

lockout plate #2, unlock and remove.

3.  Use a spanner wrench to remove the tamper-

resistant cap screws #3.

4.  Create a draw on the mixing valve by opening 

a downstream shower fixture.

Caution:

 When maintaining and adjusting the mix-

ing valve, the delivered flushing fluid temperature 

shall be 60°F (15°C) to 95°F (35°C). In circum-

stances where chemical reaction is accelerated 

by flushing fluid temperature, a medical advisor 

should be consulted for the optimum temperature 

for each application.

Note:  

Valve must be installed with check valves. 

If shut off valves are installed in the shower line 

for maintenance purposes, provisions shall be 

made to prevent unauthorized shut off.

 Valve 

 

 Number  A 

D

 SV160 

11

 

9

 

8

 

4

1

/

4

DIMENSIONS:

www.tepid.com

CAPACITIES – SERIES SV160

  

 

Pressure Drop PSI  

5

 

10

 

20

 

30

 

45

 

Tempered Flow   

25

 

35

 

50

 

60

 

72

  Cold Water Bypass 

14

  

20

 

28

 

40

 

45

D

V2

V1

#3 CAP SCREWS

SAFETY LATCH

#1 PADLOCK (optional)

#2 LOCKOUT PLATE

                    (optional)

30

40

50

60

70 80

90

110

120

130

30

40

50

60

70 80

90

110

120

130

30

40

50

60

70 80

90

110

120

130

1”

4 N.P.T.

COLD

INLET

N.P.T.

HOT

INLET

1”

4

A

B

C

1

1

N.P.T. TEMPERED 

OUTLET

1”

4

1

T2

T3

T1

5330 East 25th Street 
Indianapolis Indiana 46218
Phone: (888) 445-4142

ASSE 1071 Approved

Reviews: