Stingray SV107 Series Installation & Maintenance Manual Download Page 1

Series SV107

Emergency Eye Wash Valve

(1)

Installation &

Maintenance Manual

M EFV D

Setting the Mixing Valve

Caution:

 When maintaining and adjusting the mix-

ing valve, all fixtures should be isolated from use.     

Stingray Systems recommends that you work safely 

at  all  times  and  in  a  manner  consistent  with  the 

OSHA  Lock/Tagout  standard,  29  CFR  1910.147 

and other applicable standards.

This  mixing  valve  has  been  set  at  the  factory  

to deliver 85°F outlet flow. Should the valve require 

adjustment, or an application require a different set 

temperature, proceed as follows:
1.  Contact the proper medical and safety authorities 

to  determine  the  correct  water  temperature  for 

the specific application (ie. chemicals).

2.  Remove the rounded cover nut on front of the 

valve body.

3.  Create a draw on the mixing valve by opening a 

downstream eye wash fixture.

4.  Insert a 

5

/

32

 allen key into the stem opening of 

the valve and seat in the adjustment screw (not 

shown). Set the outlet temperature by turning the 

adjustment screw clockwise to reduce tempera-

ture, counterclockwise to increase temperature. 

Use the dial thermometer to measure the outlet 

temperature.

5.  Replace rounded cover nut.
 

Operating Principle

This Series SV107 Emergency Eye Wash/Face Wash 

mixing valve is made of a thermostat element with 

a stainless steel sliding piston and liner housed in a 

bronze casting. The thermostatic cartridge responds 

to  temperature  changes  in  the  hot  and  cold  water 

supplies. In the event the thermostatic element fails 

or the hot water supply fails, the valve will provide 

full cold water bypass flow.
Note:  Valve must be installed with check valves.  

If shut off valves are installed in the shower line 

for maintenance purposes, provisions shall be 

made to prevent unauthorized shut off.

Caution:

 When maintaining and adjusting the mix-

ing valve, the delivered flushing fluid temperature 

shall  be  60°F  (15°C)  to  95°F  (35°C).  In  circum-

stances  where  chemical  reaction  is  accelerated 

by  flushing  fluid  temperature,  a  medical  advisor 

should be consulted for the optimum temperature 

for each application.

www.tepid.com

CAPACITIES – MODEL SV107

  

  Pressure Drop PSI  

5  10  20  30  45

 

Tempered Flow   

2 

3 

5 

7  10

  Cold Water Bypass 

1   2 

4 

5 

7

30

40

50

60

70 80

90

110

120

130

ASSE 1071 Approved