COMMISSIONING

Programming unit

 

» WPM G

Summary of Contents for WPM G

Page 1: ...COMMISSIONING Programming unit WPM G ...

Page 2: ...e 5 5 3 Network connection 5 5 4 Commissioning cascades 6 5 5 Manual test 8 6 Controller menu 8 Alarms 8 Settings 9 Language 9 System settings 9 Installation 9 Heating 10 Room temperature sensor 11 DHW 11 Pool 12 Cooling 12 DHW draw off control 14 Water charging system 14 Booster heater 15 Hot gas 15 Mixing valves 16 Buffer cylinder 17 Alarm control central alarm 18 Current limiter 18 Flow switch ...

Page 3: ...s information may result in non seri ous or minor injury 1 3 Other symbols in this documentation Note General information is identified by the adjacent symbol f f Read these texts carefully Symbol Meaning Material losses appliance damage consequential losses and environmen tal pollution Appliance disposal f f This symbol indicates that you have to do something The ac tion you need to take is descr...

Page 4: ... values on the current menu page are reset to the factory settings Activate or deactivate functions The symbol shows the activated function Activate or deactivate functions The symbol shows the deactivated function Select one of two options Symbol Meaning Select one of two options Receive further information 5 Commissioning Note If the heat pump needs to be restarted the symbol is shown on the dev...

Page 5: ...tion instructions When using the ISG use the static IP address 5 3 1 Connecting to the internet f f Connect a patch cable to the RJ45 connector see chapter Commissioning Connecting to the internet in the operat ing and installation instructions for the heat pump 5 3 2 Network settings Note f f If multiple heat pumps are installed the network settings must be entered separately for each heat pump N...

Page 6: ...cascade control f f Press the button to return to the higher ranking menu f f Tap the button to access the Cascade control menu f f Select the Cascade control menu on the primary heat pump f f Set the slide toggle to Master 1 f f Make the required settings f f Confirm the selection f f Select the Cascade control menu on the secondary heat pump f f Set the slide toggle to Slave 0 f f Assign a heat ...

Page 7: ... secondary heat pump is registered under a different ID In the settings change the ID to the first assigned ID or re start the primary heat pump ID already regis tered The ID has been as signed to another sec ondary heat pump Change the ID Multiple errors Several of the above messages are active Correct the faults one after the other The corresponding secondary heat pump must be reconnected manual...

Page 8: ... Some setting options are only available in safe mode Once you have entered the access code it does not need to be re entered for eight hours The remaining time is displayed top left of the screen Note Certain menu items are protected by a code The code set at the factory is 607080 Alarms Settings Language System settings Installation Heating Room temperature sensor DHW Pool Cooling DHW draw off c...

Page 9: ...Older data is not displaced f f Insert a USB stick into the USB port f f Activate the Logging function Logging starts f f If the menu cannot be activated remove the USB stick Re turn to the menu Insert the USB stick into the USB port f f If the menu still cannot be activated replace the USB stick f f If you want to terminate logging deactivate the Logging function A message appears when logging ha...

Page 10: ...t f f Activate or deactivate the function Buffer cylinder f f Activate or deactivate the function When the function is activated there is a buffer cylinder in the heating system f f If the buffer cylinder is to be charged with a certain tempera ture install a buffer sensor Flow switch Note If no flow switch is connected but the function is activat ed the heat pump will not start Note Several flow ...

Page 11: ...a fixed temperature independently of the heating curve Set flow temp f f Set the temperature to which the flow is heated in Fixed value operation System return temperature sensor f f Activate or deactivate the function Room temperature sensor Activate room sensor Passive 0 active 1 Room temperature sensor influence Activate room sensor f f Activate or deactivate the function When the function is a...

Page 12: ...et pool temperature f f Set the water temperature to which the pool should be heat ed Pool hysteresis f f Set the temperature deviation from the set temperature at which heating of the swimming pool water starts Example Pool hysteresis 1 K Set pool temperature 20 C Start swimming pool heating 18 5 C End swimming pool heating 21 5 C Required heating temperature f f Set the flow temperature at which...

Page 13: ...s cooled actively The corresponding symbol appears in the main menu The symbol allows you quick access to this menu Surplus heat Brine 1 cooler 2 Can only be adjusted if the Active cooling function is activated f f Set whether the excess heat should be discharged into the borehole or via the air cooler Summer mode cooling temperature f f Set the outside temperature from which the rooms will be coo...

Page 14: ...HW draw off temp f f Set the temperature to be supplied at the draw off points Alarm limit DHW f f Set a temperature which will trigger the display of a fault message on the device when reached This function prevents too high DHW temperatures at the draw off points Alarm delay DHW f f Set a time after which a fault message is displayed on the device This function delays the appearance of a fault m...

Page 15: ...nd Temporarily deactivate external booster heater f f Activate or deactivate the function Outside temperature dependent f f Activate or deactivate the function When this function is activated the booster heater is activated at the set outside temperature Outside temperature limit Can only be adjusted if the Outside temperature dependent function is activated f f Set the outside temperature from wh...

Page 16: ...r Heating circuit 1 Activate heating circuit 1 f f Activate or deactivate the function When the function is activated the settings made here apply for the corresponding heating circuit The corresponding symbol ap pears in the main menu The symbol allows you quick access to this menu When the function is deactivated the higher ranking settings are used to control the heating circuit Type f f Choose...

Page 17: ...ated Buffer cylinder Buffer cylinder type Buffer cylinder temperature automatic mode Buffer cylinder overcharge Required buffer temperature Booster heater increase Booster heater max application limit Buffer cylinder configuration Heat pump start offset Booster heater start offset Summer mode permissible Parameter Unit Buffer cylinder temperature C Current temperature in buffer cylinder System flo...

Page 18: ...te the function When the function is activated the contents of the buffer cylinder are heated when the set temperature deviation is reached Heat pump start offset Can only be adjusted if the Start at fixed temperature offset function is activated f f Set the temperature deviation at which the heat pump should cover the heat demand Booster heater start offset Can only be adjusted if the Start at fi...

Page 19: ...ing from the heat pump If the tem perature falls below the set value the brine pump and the com pressor are switched off Brine alarm f f Activate or deactivate the function When this function is activated a fault message is displayed on the device if the set temperature is undershot Evaporator frost protection active f f Activate or deactivate the function Min brine outlet Can only be adjusted if ...

Page 20: ...d mode f f Set the temperature at which DHW heating ends DHW start temperature maximum mode f f Set the temperature at which DHW heating starts DHW stop temperature maximum mode f f Set the temperature at which DHW heating ends Cascade control Cascade control Slave 0 Master 1 WPE I H Premium heat pumps Number of secondary WPE I H Premium Ext controllable heat pumps Heat pump ID Port number Paramet...

Page 21: ... pump ID 1 to the secondary heat pump As sign IDs in chronological order for further secondary heat pumps Port number Building management system BMS Activate BMS Modbus mode Address Baud rate Parity Stop bits Port number Parameter Number of stop bits The heat pump can be monitored and controlled via a Modbus The heat pump sends data to the Modbus on request Activate BMS f f Activate or deactivate ...

Page 22: ...mum compressor stage f f Set the minimum compressor stage Maximum compressor stage f f Set the maximum compressor stage Maximum flow temperature f f Set the maximum flow temperature Maximum return temperature f f Set the maximum return temperature Compressor start delay f f Set the time after which the compressor will start Circulation pumps System pump Enable system circulation pump Circulation p...

Page 23: ...valve on off Heat surplus diverter valve on off Pump overheating Heat surplus fan Enable surplus heat dissipation Opening level surplus heat dissipation Heating circuit 2 3 4 5 pump on off Heating circuit 2 mixing valve opening level 3 4 5 DHW draw off control pump Opening level DHW draw off control mixing valve DHW draw off control booster heater Water charging system pump unit Opening level wate...

Page 24: ...switched on f f Activate or deactivate the function When the function is activated the booster heater starts Booster heater opening level f f Set the output level at which the booster heater should run Ext heat generator pump Can only be adjusted if the Booster heater function is activated f f Activate or deactivate the function Ext heat generator pump on off Can only be adjusted if the Ext heat g...

Page 25: ...diverter valve on off f f Activate or deactivate the function When this function is activated the diverter valve switches Pool pump on off f f Activate or deactivate the function When the function is activated the pump starts Pool mixing valve opening level f f Set the mixing valve opening level Manually activate expansion valve f f Activate or deactivate the function When this function is activat...

Page 26: ...ump WP DHW valve Expansion valve opening level System pump Hot gas pump Heating circuit Circulation pump Heating circuit Mixing valve Booster heater Heating on off Booster heater Heating 0 10 V Booster heater Circulation pump faulty Digital inputs Flow switch Digital inputs SMART GRID 1 Digital inputs SMART GRID 2 Digital inputs Brine pump external start DHW draw off control Mixing valve DHW draw ...

Page 27: ...heat pump are live If the primary heat pump is switched off the secondary heat pumps are also switched off If the secondary heat pump is switched off the status is sent to the primary heat pump Restart A restart is required after changes have been made to certain parameters in the menu The heat pump can only be re started when it is in standby mode Service mode The heat pump is not in operation Fr...

Page 28: ...sioning Appendix 28 WPM G www stiebel eltron com Appendix Operating mode 7 Appendix 7 1 Hydraulic connection diagram Option 1 4 2 Mo 53 01 01 I P mbar T33 T35 K503 T31 T34 Konfiguration 1 III T W AO24 FR5 T32 ...

Page 29: ...Commissioning Appendix www stiebel eltron com WPM G 29 Option 2 4 2 Mo 53 01 01 I P mbar T35 Konfiguration 2 III T W AO24 FR5 T32 T31 T34 T33 ...

Page 30: ...Commissioning Appendix 30 WPM G www stiebel eltron com Option 3 Konfiguration 3 4 2 Mo 53 01 01 I P mbar T35 T31 T34 III T W AO24 FR5 T32 FR6 AO25 T33 ...

Page 31: ...Commissioning Appendix www stiebel eltron com WPM G 31 Option 4 4 2 Mo 53 01 01 I P mbar T35 T31 III III T W T W T33 AO25 FR6 K503 T32 AO24 FR5 T34 Konfiguration 4 ...

Page 32: ...er circuit 1 AO25 Dual mode mixer HG2 FR5 Circulation pump heating circuit 1 FR6 Circulation pump system K503 2nd heat generator heating T31 Buffer cylinder sensor T32 Flow sensor mixer circuit 1 T33 System flow sensor T34 System return sensor T35 Sensor outside temperature ...

Page 33: ...www stiebel eltron com WPM G 33 NOTES ...

Page 34: ...34 WPM G www stiebel eltron com NOTES ...

Page 35: ...www stiebel eltron com WPM G 35 NOTES ...

Page 36: ...ron cz www stiebel eltron cz Finland STIEBEL ELTRON OY Kapinakuja 1 04600 Mäntsälä Tel 020 720 9988 info stiebel eltron fi www stiebel eltron fi France STIEBEL ELTRON SAS 7 9 rue des Selliers B P 85107 57073 Metz Cédex 3 Tel 0387 7438 88 Fax 0387 7468 26 info stiebel eltron fr www stiebel eltron fr Hungary STIEBEL ELTRON Kft Gyár u 2 2040 Budaörs Tel 01 250 6055 Fax 01 368 8097 info stiebel eltron...