INSTallaTION
Installation
8
| WPE-I H(K) 230 Premium
www.stiebel-eltron.com
8.3 Minimum clearances
≥500
≥50
≥500
≥500
≥1000
D
00000
34
46
9
f
f
Maintain the minimum clearances to ensure trouble-free op-
eration of the appliance and facilitate maintenance work.
8.4 Electrical installation
WARNING Electrocution
Carry out all electrical connection and installation work
in accordance with national and regional regulations.
WARNING Electrocution
The connection to the power supply must be in the form
of a permanent connection. Ensure the appliance can be
separated from the power supply by an isolator that dis-
connects all poles with at least 3 mm contact separation.
This requirement can be met by using contactors, circuit
breakers, fuses/MCBs, etc.
Note
The specified voltage must match the mains voltage. Ob-
serve the type plate.
!
Material losses
Provide separate fuses/MCBs for the two power circuits,
i.e. for the compressor and the electric emergency/boost-
er heater circuits.
f
f
Use cables with the relevant cross-sections. Observe the ap-
plicable national and regional regulations.
WPE-I 04 H(K) 230 Premium | WPE-I 06 H(K) 230 Premium |
WPE-I 08 H(K) 230 Premium
fuse protec-
tion
assignment
Cable cross-section
B 16 A
Compressor
2.5 mm² for routing through a wall
1.5 mm² when routing on a wall or in an
electrical conduit on a wall
B 16 A
Electric emergency/
booster heater (BH)
2.5 mm²
1.5 mm² with only two live cores and
routing on a wall or in an electrical con-
duit on a wall.
B 16 A
Control unit
1.5 mm²
WPE-I 12 H(K) 230 Premium | WPE-I 15 H(K) 230 Premium
fuse protec-
tion
assignment
Cable cross-section
B 25 A
Compressor
4.0 mm² when routing in a wall
2.5 mm² when routing above the surface
B 16 A
Electric emergency/
booster heater (BH)
2.5 mm²
1.5 mm² with only two live cores and
routing on a wall or in an electrical con-
duit on a wall.
B 16 A
Control unit
1.5 mm²
Electrical data is provided in the chapter "Specification / Data
table".
Note
The appliance includes an inverter for the variable speed
compressor. In the event of an error, inverters can cause
DC residual currents. If RCDs are provided, they must be
type B AC/DC-sensitive.
A DC residual current can block type A RCDs.
f
f
Ensure that the appliance power supply is discon-
nected from the distribution board.
9. Installation
9.1 Transport
f
f
Transport the appliance in its packaging to protect it against
damage.
f
f
Protect the appliance against heavy impact during transport.
- If the appliance needs to be tilted during transport, this must
only be for a short time and it must only be tilted on one of
its longitudinal sides.
The longer the appliance is tilted, the greater the distribution
of refrigerant oil inside the system.
- Storage and transport at temperatures below - 20 °C and
above + 50 °C are not permissible.
Summary of Contents for WPE-I 04 H 230 Premium
Page 21: ...Installation Maintenance www stiebel eltron com WPE I H K 230 Premium 21 ...
Page 27: ...Installation Specification www stiebel eltron com WPE I H K 230 Premium 27 ...
Page 31: ...Installation Specification www stiebel eltron com WPE I H K 230 Premium 31 ...
Page 47: ...www stiebel eltron com WPE I H K 230 Premium 47 NOTES ...